component
Switch for terminating
resistor
Available Modbus
addresses
Configurable baud rate You can set the baud rate using the software under "P-INTERFACE/P-Fieldbus/P-Profibus/Modbus/
Configurable parity
Configurable interface
type
LED "Status"
(above the DIL
switches, only visible if
the blue cover is
removed)
Installation and operating instructions Sinamics G180
Operating Instructions, 05/2013, 4BS0751-001
Function
A bus line must be terminated with a terminating resistor. A terminating resistor can be fitted in the
connector. Select the switch position accordingly. Switch up = resistor On
You can set the Modbus address using the software as follows:
A value from 0 ... 247 can be set under "P-INTERFACE/P-Fieldbus/P-Profibus/Modbus/P-Modbus
RTU/BUS address".
If you specify the value 0, the address will be set by the hardware. In this case, set a binary address
from 1 to 127 with the DIL switches. (Switch 1 is MSB, switch 7 is LSB)
P-Modbus RTU/Baudrate".
If you specify the value 0 under "P-INTERFACE/P-Fieldbus/P-Profibus/Modbus/P-Modbus RTU/
BUS address", then the hardware will set the baud rate. Set the binary baud rate according to the
following list:
● 000: not available
● 001: 1200
● 010: 2400
● 011: 4800
● 100: 9600
● 101: 19,200 (standard for RTU)
● 110: 38.400
● 111: 57.600
You can set the parity using the software under "P-INTERFACE/P-Fieldbus/P-Profibus/Modbus/P-
Modbus RTU/Parity".
If you specify the value 0 under "P-INTERFACE/P-Fieldbus/P-Profibus/Modbus/P-Modbus RTU/
BUS address", then the hardware will set the parity. Set the binary parity according to the following
list:
● 00: not available
● 01: none (standard for RTU)
● 10: even
● 11: odd
Set this switch according to the interface you want to use.
● 0: RS 485
● 1: RS 232
Flashing red at different
frequencies
Flashing green at 1 Hz,
0.5 s on, 0.5 s off
Flashing green at 2 Hz,
0.25 s on, 0.25 s off
Hardware error on the Modbus board: Contact the service
department.
Initialization of the Modbus board OK
Initialization of the Modbus board has errors: Contact the service
department.