Electronic Shutdown For "Safe Halt" / Ptc Inputs; Standards For Electronic Shutdown; General Information About Electronic Shutdown; Motor Temperature Monitoring Shutdown Concept - Siemens SINAMICS G180 Installation And Operating Instructions Manual

Compact inverter units, cabinet systems, air-cooled and liquid-cooled cabinet units
Hide thumbs Also See for SINAMICS G180:
Table of Contents

Advertisement

2 analog outputs (AO)
Power supply unit, 24 V, 300 mA
In addition to the main board, the peripheral boards two and four are also fitted with a
daughterboard which contains the circuitry for the PTC thermistor inputs.
The connection diagram of these variants can be found in the section "Control cable terminals
"peripheral board 1" (Page 120).
Use the digital inputs and the analog outputs of the peripheral board corresponding to the
inputs and outputs on the main terminal block. Further information can be found in the section
"Standard control cable terminals" (Page 119).
Configure the three relay outputs corresponding to the relay outputs of the main terminal block.
For further information about galvanic isolation, refer to section "Safe isolation in accordance
with EN 61800-5-1" (Page 97).
10.2.2

Electronic shutdown for "Safe halt" / PTC inputs

10.2.2.1

Standards for electronic shutdown

The electronic shutdown complies with the following standards:
● DIN EN ISO 12100, Safety of machinery, Part 1 and 2
● DIN EN 954, Safety-related parts of control systems, Parts 1 and 2
● DIN EN ISO 14121, Guidelines to assess risk (draft standard)
● EN 50281, Electrical apparatus for use in the presence of combustible dust
● EN 60079, Electrical apparatus for explosive gas atmospheres according to VDE 0165,
10.2.2.2

General information about electronic shutdown

Using the electronic shutdown concept of the inverter, a system without main contactor can
be shut down. This also applies for the operation of motors in the Ex-Zone 1. In the case of a
fault, the inverter interrupts the power supply to the motor electronically.
10.2.2.3

Motor temperature monitoring shutdown concept

Principle of operation
The peripheral board 2 / 4 evaluates the measure motor temperature using a PTC thermistor.
The board ensures safety and reliability using the installed short-circuit detection. The "Safe
Installation and operating instructions Sinamics G180
Operating Instructions, 05/2013, 4BS0751-001
except mine workings