Figure 10-4
Table 10-3
Profibus circuit board - external elements
component
LED "Status" (only just
visible under the grey
cover)
LED "Online"
LED "Offline"
PROFIBUS connection Sub-D female connector for Profibus
Switch for terminating
resistor
Available PROFIBUS
addresses
LED "bus diagnostics"
Installation and operating instructions Sinamics G180
Operating Instructions, 05/2013, 4BS0751-001
PROFIBUS connection
Switch for terminating resistor
PROFIBUS address, configurable
LED "bus diagnostics"
LED "Offline"
Unused LED
LED "Online"
Profibus circuit board
Function
Flashing red at different frequencies
Flashing green at 1 Hz,
0.5 s on, 0.5 s off
Flashing green at 2 Hz,
0.25 s on, 0.25 s off
This green LED lights if the bus connection is OK.
This red LED lights if the bus connection is interrupted. Check the external bus configuration.
A bus line must be terminated with a terminating resistor. Note that a terminating resistor can also
be present in the connector and select the switch position accordingly. Switch up = resistor On.
Only one terminating resistor is permitted at the end of a Profibus line.
You can set the Profibus address using the software as follows:
A value from 0 to 125 can be set under "P-INTERFACE/P-Fieldbus/P-Profibus/Modbus/P-Profibus/
BUS address".
If you specify the value 0, the address will be set by the hardware. In this case, set an address in
the range 0 to 99 using a screwdriver.
Flashing at 1 Hz, 0.5 s On, 0.5 s Off
Flashing at 2 Hz, 0.25 s On, 0.25 s Off
Flashing at 4 Hz, 0.12 s On, 0.12 s Off
Off
Spare parts and accessories
Hardware error on the Profibus circuit board:
contact Customer Service.
Initialization of the Profibus circuit board OK
Initialization of the Profibus circuit board has
errors: contact Customer Service.
Error in the input/output configuration
Error in the length of the Profibus telegram
Error in the initialization of the Profibus
No bus fault
10.14 Profibus DP