Download Print this page

Advertisement

Advertisement

loading

Summary of Contents for Siemens SINAMICS G180

  • Page 3 ___________________ Introduction ___________________ Safety instructions ___________________ SINAMICS List of messages Assignment of the message ___________________ groups for the bit generators SINAMICS G180 Display messages ___________________ Service & Support ___________________ List of abbreviations ___________________ ___________________ Software Version 11C0242/CR88 05/2020 4BS0576F-004...
  • Page 4 Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
  • Page 5: Table Of Contents

    Table of contents Introduction ..............................5 Safety instructions ............................. 7 Security information ........................7 List of messages ............................9 Assignment of the message groups for the bit generators ............... 43 Service & Support ............................ 55 List of abbreviations ..........................57 Index ................................
  • Page 6 Table of contents Display messages 05/2020, 4BS0576F-004...
  • Page 7: Introduction

    1. Check the current software version on the inverter display in the menu "I INVERTER DATA/I device data/Version". 2. If the inverter software is higher than the version of the operating manual, download the current version from www.siemens.com. Contact the Service Department of the manufacturer for more detailed information. Display messages...
  • Page 8 Introduction Display messages 05/2020, 4BS0576F-004...
  • Page 9: Safety Instructions

    In order to protect plants, systems, machines and networks against cyber threats, it is necessary to implement – and continuously maintain – a holistic, state-of-the-art industrial security concept. Products and solutions from Siemens constitute one element of such a concept.
  • Page 10 Safety instructions 2.1 Security information Display messages 05/2020, 4BS0576F-004...
  • Page 11: List Of Messages

    List of messages Msg- Display line 1 Display line 2 Text for event memory entry Fault sup- Description Number pression on 1004 Switch interlock active The FI is in the start-inhibiting status. Set the OFF1-command or set pa- rameter "P-INV. BEHVIOUR:Switch interlock" to "off " (for operation via field bus however there is always an OFF1-command required ) 1006 !! Emergency stop !!
  • Page 12 List of messages Msg- Display line 1 Display line 2 Text for event memory entry Fault sup- Description Number pression on 2037 ! Parameter fault ! Tacho 2-track At pulse input -X2:27…29 a parameterization with a too high frequency is selected which the input-hardware is not able to detect.
  • Page 13 List of messages Msg- Display line 1 Display line 2 Text for event memory entry Fault sup- Description Number pression on 2095 !! Prewarning !! T-cooler 4 too high Wrg>T-Cool.4 t.hi Temperature at the dissipator 4 too high prewarning temperature depend- ing on the device).
  • Page 14 List of messages Msg- Display line 1 Display line 2 Text for event memory entry Fault sup- Description Number pression on 2108 !! Prewarning !! T-cooler 1 too low Wrg>T-Cool.1 t.lo Temperature at the measuring point 1 of the dissipator too low (warning at 0°C).
  • Page 15 List of messages Msg- Display line 1 Display line 2 Text for event memory entry Fault sup- Description Number pression on 2116 !! Prewarning !! P-Warning1/T = This is a user-defined warning. It is parameterized as per Cabinet heater Wrg>CabinetHeater, "P-WARNINGS/P-Warning1/T = Text selection values".
  • Page 16 List of messages Msg- Display line 1 Display line 2 Text for event memory entry Fault sup- Description Number pression on 2118 !! Prewarning !! P-Warning 3/T= as no. 2116 as no. 2116 P-Warning 3: as no. 2116 2119 !! Prewarning !! P-Warning 4/T= as no.
  • Page 17 List of messages Msg- Display line 1 Display line 2 Text for event memory entry Fault sup- Description Number pression on 2145 !!Suppressed fault!! EarthCurrentMetering FtS>I-EarthMeter. All fault messages with the text !!Suppressed fault!! are faults that are normally causing a cutoff. By parameterizing function "P-MONITORING/P-Fault suppression/T = Text selection values", these monitoring actions however do no longer cause a cutoff but only provide an indication on the display.
  • Page 18 List of messages Msg- Display line 1 Display line 2 Text for event memory entry Fault sup- Description Number pression on 2177 !!Suppressed fault!! Set/act-sign FtS>Set/act-sign ditto 2178 !!Suppressed fault!! MainCntctr FtS>Main contctr. ditto 2179 !!Suppressed fault!! Undervoltage FtS>Undervoltage ditto 2180 !!Suppressed fault!! MainsPhaseRectifier1...
  • Page 19 List of messages Msg- Display line 1 Display line 2 Text for event memory entry Fault sup- Description Number pression on 2190 !!Suppressed fault!! P-failure 1/T = ditto Cabinet heater, FtS>CabinetHeater, Motor heater, FtS>Motor heater, MotorBearingTemp., FtS>M-BearingTemp, MotorWindingTemp., FtS>M-WindingTemp, Insulation Fault, FtS>InsulationFtS, Fan external, FtS>Fan external,...
  • Page 20 List of messages Msg- Display line 1 Display line 2 Text for event memory entry Fault sup- Description Number pression on 2193 !!Suppressed fault!! P-failure 4/T= as no. 2190 as no. 2190 ditto 2194 !!Suppressed fault!! P-failure 5/T= as no. 2190 as no.
  • Page 21 List of messages Msg- Display line 1 Display line 2 Text for event memory entry Fault sup- Description Number pression on 2264 !!Suppressed fault!! Overcurrent V FtS>Overcurr. V ditto 2265 !!Suppressed fault!! Overcurrent W FtS>Overcurr. W ditto 2266 !!Suppressed fault!! Zero trace faulty FtS>Zero trace ditto...
  • Page 22 List of messages Msg- Display line 1 Display line 2 Text for event memory entry Fault sup- Description Number pression on 2645 !! Fault !! Zero trace faulty Flt>Zero trace as no. 2545, but not retained 3000 !! Inverter fault !! download texts IF>download texts The transmission of another display language from IMS to the inverter...
  • Page 23 List of messages Msg- Display line 1 Display line 2 Text for event memory entry Fault sup- Description Number pression on 3010 !! Inverter fault !! Current asymmetry W IF>C-asymmetry W This fault can occur only at inverters with several converter systems con- nected in parallel, if the current of one system is so asymmetric in phase W, that the system becomes overloaded.
  • Page 24 List of messages Msg- Display line 1 Display line 2 Text for event memory entry Fault sup- Description Number pression on 3022 !! Inverter fault !! Temp.Sensor Cool.2 IF>TmpSens.Cool.2 Fault in temperature sensor for dissipator 2. Thermistor –B2 to input of PCB Signals –A13- X52:1-2 has a short or a disconnection.
  • Page 25 List of messages Msg- Display line 1 Display line 2 Text for event memory entry Fault sup- Description Number pression on 3032 !! Inverter fault !! InputReactor 2 IF>InpReactor 2 low/ mean The temperature of the input reactor L8.2 is too high. Clean the air filter; recheck the fans of the device.
  • Page 26 List of messages Msg- Display line 1 Display line 2 Text for event memory entry Fault sup- Description Number pression on 3060 !! Fault !! Interr. RS485 (X26) Flt>RS485 (X26) The fault occurs if: - the external display is not correctly connected to the RS485 interface -X26 or if it is disconnected - at "P-INTERFACES/P-RS485(X26)=failure"...
  • Page 27 List of messages Msg- Display line 1 Display line 2 Text for event memory entry Fault sup- Description Number pression on 3084 !! Fault !! T-cooler 4 too low Flt>T-Cool.4 t.lo Temperature at dissipator 4 too low (cut-off at -5° C). Heat up the operation environment;...
  • Page 28 List of messages Msg- Display line 1 Display line 2 Text for event memory entry Fault sup- Description Number pression on 3105 Fault SC phase U Flt>Short Ph.U Short in inverter phase U; repair short in conductor inverter output/motor or within the motor;...
  • Page 29 List of messages Msg- Display line 1 Display line 2 Text for event memory entry Fault sup- Description Number pression on 3128 Fault MainsPhaseRectifier2 Flt>MainsPh.Rec.2 high A mains phase at inverter rectifier 2 has failed: recheck the mains fuses; measure the line voltage. 3129 Fault Interruption BUS...
  • Page 30 List of messages Msg- Display line 1 Display line 2 Text for event memory entry Fault sup- Description Number pression on 3133 Fault Diff. current input Flt>DiffCurr high The summation current transformer –T20 has tripped. An earth current of min. 2…4A is flowing (depending on the device). Check where the earth fault is located.
  • Page 31 List of messages Msg- Display line 1 Display line 2 Text for event memory entry Fault sup- Description Number pression on 3180 Fault P-Failure1/T = mean This concerns a user defined fault. It is parameterized acc. to Cabinet heater, Flt>CabinetHeater, "P-FAILURES/P-Failure1/T = Text selection values".
  • Page 32 List of messages Msg- Display line 1 Display line 2 Text for event memory entry Fault sup- Description Number pression on 3183 Fault P-failure 4/T= as no. 3180 as no. 3180 mean P-failure 4: as no. 3180 3184 Fault P-failure 5/T= as no. 3180 as no.
  • Page 33 List of messages Msg- Display line 1 Display line 2 Text for event memory entry Fault sup- Description Number pression on 3206 !! Inverter fault !! Power section W-! IF>Power.Sect.W- as no. 3006, but not retained 3207 !! Inverter fault !! Braking transistor IF>BrakeTransist.
  • Page 34 List of messages Msg- Display line 1 Display line 2 Text for event memory entry Fault sup- Description Number pression on 3236 !! Inverter fault !! EarthCurrentMetering IF>I-EarthMeter. as no. 3036, but not retained 3237 !! Inverter fault !! Ter. X81:13 inactiv IF>X83:13 inactiv as no.
  • Page 35 List of messages Msg- Display line 1 Display line 2 Text for event memory entry Fault sup- Description Number pression on 3314 !! Fault !! T-CPU too low Flt>T-CPU too low as no. 3114, but not retained 3315 !! Fault !! T-cooler too high Flt>T-Cool.
  • Page 36 List of messages Msg- Display line 1 Display line 2 Text for event memory entry Fault sup- Description Number pression on 3392 !! Fault !! Interruption RS485 Flt>InterrpRS485 The fault occurs if: - the external display is not correctly connected to the RS485 interface or if it is disconnected - at P-INTERFACES/ P-RS485/RktRS485=failure is set and - a RS485 setpoint source is parameterized.
  • Page 37 List of messages Msg- Display line 1 Display line 2 Text for event memory entry Fault sup- Description Number pression on 3453 !! OFF 2 !! Contr. AD missing OFF2>contr. AD This error occurs when under "P-INTERFACE/P-Fieldbus/Contr. AD" the parameterized bit in the control word is not specified by your control, the reaction under "P-INTERFACE/P-Fieldbus/Rct.
  • Page 38 List of messages Msg- Display line 1 Display line 2 Text for event memory entry Fault sup- Description Number pression on 3463 !! Emergency stop !! Contr. AD missing ESt>contr. AD As message no. 3453, at "P-INTERFACES/P-Fieldbus/Rct.BUS=Emergency stop" parameterized 3464 !! Emergency stop !! Interruption RS485 ESt>InterrptRS485...
  • Page 39 List of messages Msg- Display line 1 Display line 2 Text for event memory entry Fault sup- Description Number pression on 3607 Terminal X2:8 inactive There is no ON-command parameterized to terminal -X2:8. At terminal -X2:8 however, there is inverter-internal a cutoff by hardware always avail- able.
  • Page 40 List of messages Msg- Display line 1 Display line 2 Text for event memory entry Fault sup- Description Number pression on 3618 Wait test STO Main contactor off You have manually activated the test of the two switch-off signal paths for the "Safe torque off"...
  • Page 41 List of messages Msg- Display line 1 Display line 2 Text for event memory entry Fault sup- Description Number pression on 3711 S1:1/4 off, S1:3 on? This message occurs only at IMS, when the switches are wrong, e.g. for transfer a new language to the inverter. Please switch the switches correct. 3717 Initialization in process...
  • Page 42 List of messages Msg- Display line 1 Display line 2 Text for event memory entry Fault sup- Description Number pression on 3890 P-message 1/T1 = P-message 1/T2 = This is a user defined operation message. Line without characters, Line without characters, It is parameterized as per Line with -----------------, Line witz-----------------,...
  • Page 43 List of messages Msg- Display line 1 Display line 2 Text for event memory entry Fault sup- Description Number pression on 3894 P-message 5/T1= P-message 5/T2= P-message 5: as no. 3890 as no. 3890 as no. 3890 3895 P-message 6/T1= P-message 6/T2= P-message 6: as no.
  • Page 44 List of messages Display messages 05/2020, 4BS0576F-004...
  • Page 45: Assignment Of The Message Groups For The Bit Generators

    Assignment of the message groups for the bit generators In the function of the bit generators "P-BIT GENERATOR1 to 20", you can also select message groups "MessGr ..." in addition to various single messages. The following table shows the assignment of the various messages, warnings, faults and inverter faults to the message groups. Message group Msg-Nr Text in line 1...
  • Page 46 Assignment of the message groups for the bit generators Message group Msg-Nr Text in line 1 Text in line 2 Selection text 2103 !! Prewarning !! T-heat sink asymm. Wrg>T-Cooler asym 2104 !! Prewarning !! T-CPU too low 2105 !! Prewarning !! T-CPU too high 2106 !! Prewarning !!
  • Page 47 Assignment of the message groups for the bit generators Message group Msg-Nr Text in line 1 Text in line 2 Selection text 2131 !! Prewarning !! "P-warning 16: T" Warn.function 16 2132 !! Prewarning !! "P-warning 17: T" Warn.function 17 2133 !! Prewarning !! "P-warning 18: T"...
  • Page 48 Assignment of the message groups for the bit generators Message group Msg-Nr Text in line 1 Text in line 2 Selection text 2165 !!Suppressed fault!! T-CPU too high 2166 !!Suppressed fault!! T-CPU too low 2167 !!Suppressed fault!! T-cooler too high 2168 !!Suppressed fault!! T-cooler too low...
  • Page 49 Assignment of the message groups for the bit generators Message group Msg-Nr Text in line 1 Text in line 2 Selection text 2225 !!Suppressed fault!! MainsPhaseRectifier3 2226 !!Suppressed fault!! MainsPhaseRectifier4 2228 !!Suppressed fault!! Temp.-sensor Sig.Brd 2229 !!Suppressed fault!! Temp.-sensor brkUnit 2235 !!Suppressed fault!! T-cooler 1 too low...
  • Page 50 Assignment of the message groups for the bit generators Message group Msg-Nr Text in line 1 Text in line 2 Selection text 2502 !! Fault !! "P-failure 15: T" Flt.function 15 2503 !! Fault !! "P-failure 16: T" Flt.function 16 2541 !! Fault !! Overcurrent U...
  • Page 51 Assignment of the message groups for the bit generators Message group Msg-Nr Text in line 1 Text in line 2 Selection text 3016 !! Inverter fault !! Commun.DSP->uP 3017 !! Inverter fault !! Current transformer 3018 !! Inverter fault !! Power unit unknown 3019 !! Inverter fault !!
  • Page 52 Assignment of the message groups for the bit generators Message group Msg-Nr Text in line 1 Text in line 2 Selection text 3061 !! Fault !! Diff. current motor Flt>I-diff. Motor 3075 !! Fault !! T-cabinet too low 3077 !! Fault !! T-cooler 2 too high 3078 !! Fault !!
  • Page 53 Assignment of the message groups for the bit generators Message group Msg-Nr Text in line 1 Text in line 2 Selection text 3125 Fault Diff set/act 3126 Fault Set/act-sign 3127 Fault MainsPhaseRectifier1 3128 Fault MainsPhaseRectifier2 3129 Fault Interruption BUS 3130 Fault BUS Hardware 3131...
  • Page 54 Assignment of the message groups for the bit generators Message group Msg-Nr Text in line 1 Text in line 2 Selection text 3451 !! OFF 2 !! Interruption BUS 3452 !! OFF 2 !! BUS Hardware 3453 !! OFF 2 !! Contr.
  • Page 55 Assignment of the message groups for the bit generators Message group Msg-Nr Text in line 1 Text in line 2 Selection text 4052 !! Speed OFF !! BUS Hardware 4053 !! Speed OFF !! Contr. AD missing 4054 !! Speed OFF !! Interruption RS485 4055 !! Speed OFF !!
  • Page 56 Assignment of the message groups for the bit generators Display messages 05/2020, 4BS0576F-004...
  • Page 57: Service & Support

    Service & Support Siemens Industry Online Support Technical questions or additional information n If you have any technical questions or require additional information, please contact Technical Support (https://support.industry.siemens.com/cs/ww/en/sc/2090) Please have the following data ready: • Type • Serial number You can find this data on the rating plate.
  • Page 58 +49 8531 39 222 0.06 €/min. from land lines of the German Telekom, mobile phone prices may differ). +49 8531 39 569 Technical support: driveservice.rhf.de@siemens.com Spare parts: drivespares.rhf.de@siemens.com Repair: driverepair.rhf.de@siemens.com Spare parts on the Internet: Spares on Web (www.siemens.com/sow) Display messages 05/2020, 4BS0576F-004...
  • Page 59: List Of Abbreviations

    List of abbreviations "Acorn Risc Machine": Microprocessor architecture ATEX "Atmosphère explosible": Synonym for the two EC explosion protection Directives: ATEX Product Directive 94/9/EC and ATEX Safety Directive 1999/92/EC Induction machine Beryllium oxide: toxin. Relevant for the disposal Health and safety at work regulations Regulations of the German Trade Association "Compact Disc": Optical storage medium for digital storage of music and data.
  • Page 60 List of abbreviations "Normally Closed", NC contact "Normally Opened", NO contact Line-side converter NRTL "Nationally Recognized Testing Laboratory": American testing facilities that provide product safety testing and certification services to manufacturers NYY, Cable types NYCWY Polychlorinated biphenyls: toxins. Relevant for the disposal. PELV "Protective Extra Low Voltage", protective extra-low voltage (PELV).
  • Page 61: Index

    Index Contacts, 56 More information, 55 On-site service, 55 Service Center Ruhstorf, 56 Spare parts, 55, 56 Technical support, 55, 56 Display messages 05/2020, 4BS0576F-004...