8.8 Examples / Applications
Global = functional for "Local" and "Remote"
If you use these inputs, remove the jumper.
As long as "P-INTERFACE:Reset-Source" is set to "Global" , all reset sources are always effective.
Max. current load of the control voltages:
● + 24 V DC, potential 2: 300 mA
● + 15 V DC, potential 2: 150 mA ± 10 mA
This voltage can supply a speed encoder connected at terminal ‑X101.
Remove both these jumpers if you are using peripheral boards 3 / 4. The supply is realized via ‑X2:1/3.
Figure 8-31
Control cable terminals for "Standard" application
8.8.1.2

Control cable terminals "peripheral board 1"

Figure 8-32
8.8.1.3

Control cable terminals "peripheral board 2"

Figure 8-33
120
Control cable terminals for "peripheral board 1" application
PTC inputs, suitable for motors in the Ex-zone or Non-Ex-Zone
Remove the 100 Ω resistor if these control cable terminals are in use.
Control cable terminals for "peripheral board 2" application
Installation and operating instructions Sinamics G180
Operating Instructions, 05/2013, 4BS0751-001