Technical Data Of The Direct Water Cooling - Siemens SINAMICS G180 Installation And Operating Instructions Manual

Compact inverter units, cabinet systems, air-cooled and liquid-cooled cabinet units
Hide thumbs Also See for SINAMICS G180:
Table of Contents

Advertisement

Technical data
C.9 Technical data of the direct water cooling
PTC thermistor input - Data
Overtemperature message
Short-circuit in the sensor circuit
Measuring circuit load
Voltage in the sensor circuit
Current in the sensor circuit
Voltage for measuring sensor break 11.6 V
Current for short-circuited sensor
circuit
Electrical design
Maximum cable length for PTC thermistor sensor circuit:
Cross-section 2.5 mm²
Cross-section 1.5 mm²
Cross-section 0.5 mm²
The PTC input can be used for monitoring motors in the Ex-Zone. The inverter itself must not
be installed in the Ex-Zone.
The PTC thermistor evaluation function can be deactivated by an internal switch. For this
reason, carry out the test described in section "Testing the PTC thermistor shutdown
function" (Page 141). If the result of the test is negative, contact the Service Center for advice.
C.9

Technical data of the direct water cooling

Technical data
Inverter type
2T3A-77401-200 ... 2T3A-77401-315
2T3A-77501-250 ... 2T3A-77501-400
2T3A-77601-250 ... 2T3A-77601-400
2T3A-77401-400
2T3A-77501-500
2T3A-77601-500
2T3A-77401-500 ... 2T3A-77401-630
2T3A-77501-560 ... 2T3A-77501-800
2T3A-77601-560 ... 2T3A-77601-910
If you connect several inverters in parallel, the technical data are multiplied according to the
number of systems. The water flowrate for type 2T 6 A‑7 5 69 4‑925 with four inverter systems
is e.g. 4×2000 l/h.
The water-cooled units BG SW2 and SW21 have the same cabinet width as the air-cooled units.
178
> 3.2 kΩ ... 3.8 kΩ
< 15 Ω ... 25 Ω
< 5 mW at R = 1.5 kΩ
< 2 V at R = 1.5 kΩ
< 1.5 mA at R = 1.5 kΩ
1.45 mA
Protective separation for 690 V to the other circuits according to EN 50178,
EN 61800‑5‑1
2 × 500 m
2 × 300 m
2 × 100 m
Frame size
BG SW2
BG SW21
BG SW3
Installation and operating instructions Sinamics G180
Operating Instructions, 05/2013, 4BS0751-001