8.2.3

Mode "std dids"

(D)
(S)
Figure 8-5
Control behavior for "Local" (dynamic)
● Enter the command "Speed On" and "Speed Off" using the <On> and <Off> buttons on the
● Make the setpoint value setting using the <down arrow> and <up arrow> buttons.
● Reset errors by pressing the buttons <S+I> simultaneously.
Control behavior for "Remote" (static)
● Control the operation of "Speed on" with a switch at ‑X2:10. Enter the setpoint via control
● When required use the reversing input ‑X2:16.
"Local" and "Remote" mode
● "Emerg. stop (NC)": If you open the contact at ‑X2:15, the drive decelerates down to 0
● "Reset" (NO): Reset errors and "Fast stop" using a 24 V pulse at ‑X2:14.
● "Controller release dynamic". Enable the inverter using a normally open contact at ‑X2:9.
Installation and operating instructions Sinamics G180
Operating Instructions, 05/2013, 4BS0751-001
Dynamic: Pushbutton mode
Static: Switch mode
Assignment of the control cable terminals for "std dids" mode
display.
cable terminal block ‑X2 with analog setpoint value 1.
speed along the braking ramp for emergency stop. The inverter clears all self-holding
functions.
The drive coasts to a stop if you open the contact at ‑X2:8. The inverter clears all self-holding
functions.
Operation
8.2 Standard mode settings
89