Commissioning
7.2 Checks with mains power supply and without motor
Selecting application and mode
● It is not necessary to select an application for inverters which have been fitted with a signal
● The parameter assignment is adapted in the factory when the unit is being tested and is
● Select the desired application under "P-DRIVE DATA/A", and select the desired operation
● If you would like to make other changes to the parameters, these changes can be made at
Checking mains power supply parameters
1. Set your mains rated voltage in the menu item "P-INVERTER DATA/V mains nom.".
2. For additional information, refer to the section titled "Mains connection" (Page 53).
Adapting motor data
1. Under "P-MOTOR DATA"/ first set the controller variant of the inverter or the motor type.
You can enter the following control variants:
74
controller at the factory.
stored under the menu "P-DRIVE DATA/A" in the "Factory_Settings" application.
under "P-OPERATION/Opr.".
– Use the associated wiring diagram in the Appendix for this. The "Standard" application
is set as the default at the factory.
– For additional information, refer to the section titled "Standard" application" (Page 119).
this point.
In this case, the parameter "P-DRIVE DATA/A=Standard" changes to "P-DRIVE DATA/
A=specific".
Note
Loss of all configured values
If you select other applications before the changed parameters have been saved, all
values already set will be lost. Save the changed parameters before selecting other
applications.
If necessary, set the controller / fan transformer correctly.
Installation and operating instructions Sinamics G180
Operating Instructions, 05/2013, 4BS0751-001