"Connecting external control voltage for compact devices" (Page 68) Perform the wiring in
accordance with the following plan:
Figure 8-25
Line contactor function
Table 8-8
Line contactor functions
Terminal /
Function
component
-F1
External control voltage fuse protection
-F2
Inverter output section fuse protection
-K1
Input side main contactor
Design recommendation: AC1 current of the contactor is at least the inverter input current
101, 102
External control voltage for the 230 V inverter
41, 42
Digital output for the main contactor control
U1, V1, W1
Mains power connection switched via main contactor
8
Main contactor feedback input
55
24 V DC supply voltage
Installation and operating instructions Sinamics G180
Operating Instructions, 05/2013, 4BS0751-001
Operation
8.5 Special functions
109