Operation according to "NAMUR 1"

(D)
(S)
Figure 8-7
Control behavior for "test" (dynamic)
● Enter the command "Controller release" and "CTRL.OFF" using the <On> and <Off>
● Make the setpoint value setting using the <down arrow> and <up arrow> buttons.
● Reset errors by pressing the buttons <S+I> simultaneously. The locking and the OUT input
Control behavior for "normal" (static)
● Control the operation of the controller release with a switch (NO) at ‑X2:10. Enter the
● When required use the reversing input (NO) ‑X2:16.
"Test" and "Normal" mode
● "Interlocking" (NC): The controller inhibit is activated if you open the contact at ‑X2:15. The
● "Off" (NC): You activate the controller inhibit if you remove the 24 V signal at ‑X2:11.
Installation and operating instructions Sinamics G180
Operating Instructions, 05/2013, 4BS0751-001
Dynamic: Pushbutton mode
Static: Switch mode
Assignment of the control cable terminals for "NAMUR 1" mode
buttons on the display.
on the control cable terminal block reset the control.
setpoint via control cable terminal block ‑X2 with analog setpoint value 1.
drive coasts to a stop and cannot be restarted. The inverter display shows the message
"Interlocking".
Operation
8.3 NAMUR mode settings
91