Analog Input 1 At Maximum Reference/Analog Input 2 Minimum Reference; Analog Input 2 At Minimum Reference; Analog Input 2 Maximum Reference; Analog Input 2 At Maximum Reference/Analog Input 1 Destination B - Emerson Unidrive M200 Parameter Reference Manual

Open-loop mode
Hide thumbs Also See for Unidrive M200:
Table of Contents

Advertisement

See Analog Input 1 Minimum Reference (07.061).
Parameter
07.064 Analog Input 1 At Maximum Reference
Short description
Defines the value of analog input 1 at maximum reference
Mode
Open‑loop
Minimum
-100.00
Default
100.00
Type
16 Bit User Save
Display Format
Standard
Coding
RW
See Analog Input 1 Minimum Reference (07.061).
Parameter
07.065 Analog Input 2 Minimum Reference
Short description
Defines the minimum reference for analog input 2
Mode
Open‑loop
Minimum
0.00
Default
0.00
Type
16 Bit User Save
Display Format
Standard
Coding
RW
See graph in Analog Input 1 Minimum Reference (07.061).
Analog Input 2 (07.002) can be scaled and limited using the following parameters:
Analog Input 2 Minimum Reference (07.065)
Analog Input 2 At Minimum Reference (07.066)
Analog Input 2 Maximum Reference (07.067)
Analog Input 2 At Maximum Reference (07.068)
Parameters above can be selected to limit the range of Analog Input 2 (07.002) and also scale it between the minimum and maximum reference.
If Analog Input 2 Minimum Reference (07.065) ≥ Analog Input 2 Maximum Reference (07.067) then A
Input Level is limited between Analog Input 2 At Minimum Reference (07.066) and Analog Input 2 At Maximum Reference (07.068)
Analog Input 2 (07.002) = [(Analog Input 2 At Maximum Reference (07.068) - Analog Input 2 At Minimum Reference (07.066))/(Analog Input 2 Maximum Reference (07.067) -
Analog Input 2 Minimum Reference (07.065))] x (Input level - Analog Input 2 Minimum Reference (07.065))+ Analog Input 2 At Minimum Reference (07.066).
Parameter

07.066 Analog Input 2 At Minimum Reference

Short description
Defines the value of analog input 2 at minimum reference
Mode
Open‑loop
Minimum
-100.00
Default
0.00
Type
16 Bit User Save
Display Format
Standard
Coding
RW
See Analog Input 2 Minimum Reference (07.065).
Parameter

07.067 Analog Input 2 Maximum Reference

Short description
Defines the maximum reference for analog input 2
Mode
Open‑loop
Minimum
0.00
Default
100.00
Type
16 Bit User Save
Display Format
Standard
Coding
RW
See Analog Input 2 Minimum Reference (07.065).
Parameter
07.068 Analog Input 2 At Maximum Reference
Short description
Defines the value of analog input 2 at maximum reference
Mode
Open‑loop
Minimum
-100.00
Default
100.00
Type
16 Bit User Save
Display Format
Standard
Coding
RW
See Analog Input 2 Minimum Reference (07.065).
Parameter
07.090 Analog Input 1 Destination B
Short description
Defines the secondary destination for analog input 1
Mode
Open‑loop
Minimum
0.000
Default
Type
16 Bit User Save
Display Format
Standard
Coding
RO, DE, ND, NC, PT
See Analog Input 1 Destination A (07.010).
110
Maximum
100.00
Units
%
Update Rate
Background read
Decimal Places
2
Maximum
100.00
Units
%
Update Rate
Background read
Decimal Places
2
= 0.00% whatever the input level.
i2
Maximum
100.00
Units
%
Update Rate
Background read
Decimal Places
2
Maximum
100.00
Units
%
Update Rate
Background read
Decimal Places
2
Maximum
100.00
Units
%
Update Rate
Background read
Decimal Places
2
Maximum
30.999
Units
Update Rate
Drive reset read
Decimal Places
3
Unidrive M200 Parameter Reference Guide