Menu 12 − User Functions 2 and Brake Control
Mode: Open‑loop
Menu 12 provides parameters for the following features:
1. Threshold detectors
2. Variable selectors
3. Mechanical brake controller
Parameter

12.001 Threshold Detector 1 Output

Short description
Displays the output of threshold detector 1
Mode
Open‑loop
Minimum
0
Default
Type
1 Bit Volatile
Display Format
Standard
Coding
RO, ND, NC, PT
The threshold detector functions are always active even if the source and destination are not routed to valid parameters. If the source is not a valid parameter then the source value is taken as 0. The
update rate for each of the threshold detector functions is always 4ms.
The following description is for threshold detector 1, but threshold detector 2 operates in the same way. The level of the parameter defined by Threshold Detector 1 Source (12.003) is converted to a
percentage and compared to Threshold Detector 1 Level (12.004) with hysteresis to give Threshold Detector 1 Output (12.001) as follows:
Source
Source < Lower threshold
Lower threshold ≤ Source < Upper threshold
Source ≥ Upper threshold
Lower threshold = Threshold Detector 1 Level (12.004) - (Threshold Detector 1 Hysteresis (12.005) / 2)
Upper threshold = Threshold Detector 1 Level (12.004) + (Threshold Detector 1 Hysteresis (12.005) / 2)
The output value can then be inverted with Threshold Detector 1 Output Invert (12.006) before being routed to the destination defined by Threshold Detector 1 Destination (12.007).
Parameter

12.002 Threshold Detector 2 Output

Short description
Displays the output of threshold detector 2
Mode
Open‑loop
Minimum
0
Default
Type
1 Bit Volatile
Display Format
Standard
Coding
RO, ND, NC, PT
See Threshold Detector 1 Output (12.001).
Parameter

12.003 Threshold Detector 1 Source

Short description
Defines the source paramter for threshold detector 1
Mode
Open‑loop
Minimum
0.000
Default
0.000
Type
16 Bit User Save
Display Format
Standard
Coding
RW, PT, BU
See Threshold Detector 1 Output (12.001).
Parameter

12.004 Threshold Detector 1 Level

Short description
Defines the reference level for threshold detector 1
Mode
Open‑loop
Minimum
0.00
Default
0.00
Type
16 Bit User Save
Display Format
Standard
Coding
RW
See Threshold Detector 1 Output (12.001).
192
Maximum
Units
Update Rate
Decimal Places
Threshold Detector 1 Output (12.001)
0
No change of state
1
Maximum
Units
Update Rate
Decimal Places
Maximum
Units
Update Rate
Decimal Places
Maximum
Units
Update Rate
Decimal Places
1
4ms write
0
1
4ms write
0
30.999
Drive reset read
3
100.00
%
4ms read
2
Unidrive M200 Parameter Reference Guide
Issue: 01.05.00.10