Sub-trip Reason
1
Option module initialization timed out
2
Programming error while writing menu in flash
{HF18}
3
Erase flash block containing setup menus failed
4
Erase flash block containing application menus failed
5
Incorrect setup menu CRC contained in flash
6
Incorrect application menu CRC contained in flash
The HF19 trip indicates that the drive firmware is partially or completely deleted. The drive is now in its bootloader and is
{HF19}
waiting for a new image to be downloaded using UniMConnect. Once a new image is downloaded, the drive can run normally.
When the drive is subsequently powered up a Stored HF trip is initiated where the sub-trip number is the number of the HF trip that last occurred. This trip will occur at every power-
up until it is reset. The trip can only be reset by first entering 1299 into Parameter mm.000 (mm.000). If the drive is powered up and a Stored HF trip occurs,
Onboard User Program: Enable (11.047) is reset to zero to prevent the on-board user program from running. This ensures that the user program can be changed or erased in case it
causes an HF trip at every power-up.
Trip descriptions
Trips shown in the table below can be generated either from the drive control system or from the power system. The sub-trip number which is in the form xxyzz is used to identify the
source of the trip. The digits xx are 00 for a trip generated by the control system or the number of a power module if generated by the power system. If the drive is not a multi-power
module drive then xx will always have a value of 1 if the trip is related to the power system. The y digit is used to identify the location of a trip which is generated by a rectifier module
connected to a power module. Where the y digit is relevant it will have a value of 1 or more, otherwise it will be 0. The zz digits give the reason for the trip and are defined in each trip
description.
Over Volts
OI ac
OI Brake
PSU
OHt Inverter
OHt Power
Trips Summary (numerical order)
244
OHt dc bus
Phase Loss
LF Power Comms
OI Snubber
Temp Feedback
Power Data
Unidrive M200 Parameter Reference Guide
Issue: 01.05.00.10