Analog Input 1 Scaling; Analog Input 1 Invert; Analog Input 1 Destination A; Analog Input 2 Mode - Emerson Unidrive M200 Parameter Reference Manual

Open-loop mode
Hide thumbs Also See for Unidrive M200:
Table of Contents

Advertisement

Value
Mode
Function
-6
4-20mA Stop
4-20mA with stop on current loop loss
-5
20-4mA Stop
20-4mA with stop on current loop loss
-4
4-20mA Low
4-20mA with switching to a low speed set in Analog Input 1 Preset on Current Loss (07.026) on current loop loss
-3
20-4mA Low
20-4mA with switching to a low speed set in Analog Input 1 Preset on Current Loss (07.026) on current loop loss
-2
4-20mA Hold
4-20mA with hold at level before loss on current loop loss (1)
-1
20-4mA Hold
20-4mA with hold at level before loss on current loop loss (1)
0
0-20mA
0-20mA
1
20-0mA
20-0mA
2
4-20mA Trip
4-20mA with An Input 1 Loss trip on current loss.
3
20-4mA Trip
20-4mA with An Input 1 Loss trip on current loss.
4
4-20mA
4-20mA with no action on current loop loss (input taken as 0%).
5
20-4mA
20-4mA with no action on current loop loss (input taken as 0%).
6
Voltage
Voltage input
(1) Analog input level remains at the value it had in the previous sample before the current fell below 3mA.
Parameter

07.008 Analog Input 1 Scaling

Short description
Defines the scaling factor of analog input 1
Mode
Open‑loop
Minimum
0.000
Default
1.000
Type
16 Bit User Save
Display Format
Standard
Coding
RW
See Analog I/O.
Analog Input 1 (07.001) is modified by Analog Input 1 Scaling (07.008), Analog Input 1 Offset (07.030) and Analog Input 1 Invert (07.009) before it is routed to its destination as follows:
A
= Analog Input 1 (07.001) + Analog Input 1 Offset (07.030)
1O
A
is the value after the offset has been applied and is limited between -100.00% and 100.00%
1O
A
= A
x Analog Input 1 Scaling (07.008)
1S
1O
A
is the value after the scaling and the offset have been applied and is limited between -100.00% and 100.00%
1S
If Analog Input 1 Invert (07.009) = 0 then A
A1I is the value after the invert, scaling and offset have been applied and is the final value that is routed to the destination defined by
Analog Input 1 Destination A (07.010) if Analog Input 1 Control (07.051) = 0
Analog Input 1 Destination B (07.090) if Analog Input 1 Control (07.051) > 0
Parameter

07.009 Analog Input 1 Invert

Short description
Inverts the signal for analog input 1
Mode
Open‑loop
Minimum
0
Default
0
Type
1 Bit User Save
Display Format
Standard
Coding
RW
See Analog Input 1 Scaling (07.008).
Parameter

07.010 Analog Input 1 Destination A

Short description
Defines the output parameter for analog input 1
Mode
Open‑loop
Minimum
0.000
Default
1.036
Type
16 Bit User Save
Display Format
Standard
Coding
RW, DE, PT
See Analog Input 1 Scaling (07.008).
Parameter

07.011 Analog Input 2 Mode

Short description
Defines the mode for analog input 2
Mode
Open‑loop
Minimum
6
Default
6
Type
8 Bit User Save
Display Format
Standard
Coding
RW, TE
Value
Text
6
Volt
7
dig
See Analog Input 2 (07.002).
The table below gives all the possible analogue input modes.
Value
Mode
6
Voltage
7
Digital
Unidrive M200 Parameter Reference Guide
Issue: 01.05.00.10
Maximum
Units
Update Rate
Decimal Places
= A
otherwise A
= -A
1I
1S
1I
1S
Maximum
Units
Update Rate
Decimal Places
Maximum
Units
Update Rate
Decimal Places
Maximum
Units
Update Rate
Decimal Places
Function
Voltage
Digital
10.000
Background read
3
1
Background read
0
30.999
Drive reset read
3
7
Background read
0
103