Parameter Mm.000; Possible Failures - Emerson Unidrive M200 Parameter Reference Manual

Open-loop mode
Hide thumbs Also See for Unidrive M200:
Table of Contents

Advertisement

Parameter mm.000

Parameter mm.000 (mm.000) is one parameter that can be accessed from every drive menu so that the user can initiate various actions by setting a
value in this parameter and then performing a drive reset. If the action is completed successfully parameter mm.000 is cleared when the action is
complete. If the action is not started because the value does not correspond to an action, or because the action is not allowed (i.e. an attempt is made
to load defaults and the drive is enabled), parameter mm.000 is not cleared. If the action is started and then fails a trip is produced and parameter
mm.000 is not cleared.
There could be some conflict between the actions of Parameter mm.000 (mm.000) and Parameter Cloning (11.042) when the drive is reset. If
Parameter Cloning (11.042) has a value of 1 or 2 and a valid action is required from the value of parameter mm.000 then only the action required by
parameter mm.000 is performed, but on successful completion of the action both parameters are cleared. If Parameter Cloning (11.042) has any other
value it is not affected.
The table below shows the possible actions that can be initiated with Parameter mm.000 (mm.000).
Parameter
mm.000
Action
(mm.000)
value
Save drive user save parameters to non-volatile memory. Power-
1000
down save parameters are saved when the drive enters the under
voltage state.
Save drive parameters to non-volatile memory. It should be noted
1001
that power-down save parameters are also saved which will result
in one background task scan being extended to 200ms.
1070
Reset all option modules
1233
Load 50Hz defaults
Load 50Hz defaults to all menus except option module menus (i.e
1234
15 to 20 and 24 to 28)
1244
Load 60Hz defaults
Load 60Hz defaults to all menus except option module menus (i.e
1245
15 to 20 and 24 to 28)
1299
Reset Stored HF trip.
Create a boot file on a non-volatile media card based on the
2001
present drive parameters including all Menu 20 parameters
NV media card: Transfer the drive parameters to parameter file
4xxx
xxx
NV media card: Transfer the onboard user program to onboard
5xxx
user program file xxx
NV media card: Load the drive parameters from parameter file xxx
6xxx
or the onboard user program from onboard user program file xxx
7xxx
NV media card: Erase file xxx
8xxx
NV Media card: Compare the data in the drive with file xxx
9555
NV media card: Clear the warning suppression flag
9666
NV media card: Set the warning suppression flag
9777
NV media card: Clear the read-only flag
9888
NV media card: Set the read-only flag
Only display parameters that are different from their default value.
12000
This action does not require a drive reset.
Only display parameters that are used to set-up destinations (i.e.
12001
DE format bit is 1). This action does not require a drive reset.
Deletes an onboard user program if a program is present.
59999
Note: Any parameter changes that have not been saved will be
lost during this action.
Parameter mm.000 (mm.000) values from 1 to 14 are equivalent to other values as shown in the table below to allow easy access to some commonly
used functions. For 0 and each of these values the keypad provides a string as shown.
Unidrive M200 Parameter Reference Guide
Issue: 01.05.00.10

Possible failures

No action if the drive is in the
under voltage state
No action if the drive is enabled
No action if the drive is enabled
No action if the drive is enabled
No action if the drive is enabled
Non-volatile media card trips
Non-volatile media card trips
Non-volatile media card trips
No action if the drive is enabled
Non-volatile media card trips
Non-volatile media card trips
Non-volatile media card trips
Non-volatile media card trips
Non-volatile media card trips
Non-volatile media card trips
Non-volatile media card trips
No action if the drive is
enabled.
No action if there is no program
present.
No action if the user program is
enabled (i.e.
Onboard User Program: Enable
(11.047) = 1)