08.043 24V Supply Input State
Short description
Displays the state for the 24V Supply Input
Mode
Open‑loop
Minimum
0
Default
Type
1 Bit Volatile
Display Format
Standard
Coding
RO, ND, NC, PT
Digital Input 13 (24V Supply Input) is an external 24V supply input that is monitored and can be used as a 24V digital input if an external 24V supply is not required. The state parameter is low for the voltage
range from 0V to 17V and high for the voltage range above 18V. As the input is a power supply it will consume significant current if the level is taken above 24V when the drive is running from its internal power
supply, or at any voltage level if this input is the only power supply to the drive. The 24V Input is available on the AI SD card adaptor. The 24V alarm is triggered if 24V Loss Alarm Enable (11.098) = 1 and
24V Supply Input State (08.043) = 0.
Parameter
08.044 Keypad Stop Button State
Short description
Displays the state for the Keypad Stop button
Mode
Open‑loop
Minimum
0
Default
Type
1 Bit Volatile
Display Format
Standard
Coding
RO, ND, NC, PT
See Keypad Run Button State (08.041).
Parameter

08.051 Keypad Run Button Invert/Toggle

Short description
Set to invert/toggle Keypad Run Button
Mode
Open‑loop
Minimum
0
Default
0
Type
8 Bit User Save
Display Format
Standard
Coding
RW, TE
Value
Text
0
Not.Inv
1
Invert
2
Toggle
When a button state is used to change a parameter (see Keypad Run Button Destination (08.061)) the state can be used in any one of modes selected by Keypad Run Button Invert/Toggle (08.051).
0 The parameter will be the same as the input state.
1 The parameter will be the inverse of the input state.
2 The parameter will toggle each time the state transitions from 0 to 1.
Parameter

08.052 Keypad Auxiliary Button Invert/Toggle

Short description
Set to invert/toggle Keypad Auxiliary Button
Mode
Open‑loop
Minimum
0
Default
0
Type
8 Bit User Save
Display Format
Standard
Coding
RW, TE
Value
Text
0
Not.Inv
1
Invert
2
Toggle
When a button state is used to change a parameter (see Keypad Auxiliary Button Destination (08.062)) the state can be used in any one of modes selected by Keypad Auxiliary Button Invert/Toggle (08.052).
0 The parameter will be the same as the input state.
1 The parameter will be the inverse of the input state.
2 The parameter will toggle each time the state transitions from 0 to 1.
Parameter

08.053 24V Supply Input Invert

Short description
Set to invert 24V Supply Input
Mode
Open‑loop
Minimum
0
Default
0
Type
8 Bit User Save
Display Format
Standard
Coding
RW, TE
Value
Text
0
Not.Inv
1
Invert
When a button state is used to change a parameter (see 24V Supply Input Destination (08.063)) the state can be used in any one of modes selected by 24V Supply Input Invert (08.053).
0 The parameter will be the same as the input state.
1 The parameter will be the inverse of the input state.
Parameter
08.061 Keypad Run Button Destination
Short description
Defines the destination parameter for digital input 11
Mode
Open‑loop
Minimum
0.000
Default
0.000
Type
16 Bit User Save
Display Format
Standard
Coding
RW, DE, PT
This destination parameter provides the routing for the Keypad Run (DI 11) input, see Keypad Run Button Invert/Toggle (08.051).
118
Maximum
1
Units
Update Rate
Background write
Decimal Places
0
Maximum
1
Units
Update Rate
Background write
Decimal Places
0
Maximum
2
Units
Update Rate
Background read
Decimal Places
0
Maximum
2
Units
Update Rate
Background read
Decimal Places
0
Maximum
1
Units
Update Rate
Drive reset read
Decimal Places
0
Maximum
30.999
Units
Update Rate
Drive reset read
Decimal Places
3
Unidrive M200 Parameter Reference Guide
Issue: 01.05.00.10

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents