The drive controls asynchronous machines in open loop control with respect to frequency and current. The open loop asynchronous control is further broken down into vector and fixed boost modes.
Parameter
03.001 Final Demand Reference
Short description
Displays the final reference to the frequency controller
Mode
Open‑loop
Minimum
−VM_FREQ
Default
Type
32 Bit Volatile
Display Format
Standard
Coding
RO, FI, VM, ND, NC, PT
Final Demand Reference (03.001) shows the fundamental drive frequency demand from the Post Ramp Reference (02.001) and the Hard Frequency Reference (03.022) (if enabled).
Parameter
03.005 Zero Frequency Threshold
Short description
Defines the threshold for detecting the zero frequency condition
Mode
Open‑loop
Minimum
0.00
Default
2.00
Type
16 Bit User Save
Display Format
Standard
Coding
RW, BU
If the Post Ramp Reference (02.001) is at or below the level defined by this parameter in either direction Zero Frequency (10.003) = 1, otherwise Zero Frequency (10.003) = 0.