Menu 3 − Frequency Monitoring and Speed Feedback
Mode: Open‑loop
The drive controls asynchronous machines in open loop control with respect to frequency and current. The open loop asynchronous control is further broken down into vector and fixed boost modes.
Parameter

03.001 Final Demand Reference

Short description
Displays the final reference to the frequency controller
Mode
Open‑loop
Minimum
−VM_FREQ
Default
Type
32 Bit Volatile
Display Format
Standard
Coding
RO, FI, VM, ND, NC, PT
Final Demand Reference (03.001) shows the fundamental drive frequency demand from the Post Ramp Reference (02.001) and the Hard Frequency Reference (03.022) (if enabled).
Parameter

03.005 Zero Frequency Threshold

Short description
Defines the threshold for detecting the zero frequency condition
Mode
Open‑loop
Minimum
0.00
Default
2.00
Type
16 Bit User Save
Display Format
Standard
Coding
RW, BU
If the Post Ramp Reference (02.001) is at or below the level defined by this parameter in either direction Zero Frequency (10.003) = 1, otherwise Zero Frequency (10.003) = 0.
Unidrive M200 Parameter Reference Guide
Issue: 01.05.00.10
Maximum
VM_FREQ
Units
Hz
Update Rate
16ms
Decimal Places
2
Maximum
20.00
Units
Hz
Update Rate
Background read
Decimal Places
2