Parameter

04.025 Low Frequency Thermal Protection Mode

Short description
Set to enable low frequency thermal protection mode
Mode
Open‑loop
Minimum
0
Default
0
Type
8 Bit User Save
Display Format
Standard
Coding
RW
See Motor Thermal Time Constant 1 (04.015).
Parameter

04.026 Percentage Torque

Short description
Displays the torque producing current as a percentage or motor rated current
Mode
Open‑loop
Minimum
−VM_USER_CURRENT
Default
Type
16 Bit Volatile
Display Format
Standard
Coding
RO, FI, VM, ND, NC, PT
Percentage Torque (04.026) gives the Torque Producing Current (04.002) as a percentage of the rated torque producing current for the motor, but with
an additional adjustment above rated frequency so that it gives percentage torque. Below rated frequency, Percentage Torque (04.026)
= Percentage Load (04.020). Above rated frequency, the Percentage Torque (04.026) is adjusted as follows:
Percentage Torque (04.026) = Percentage Load (04.020) x Motor Rated Frequency (05.006) / Output Frequency (05.001)
Parameter

04.036 Motor Protection Accumulator Power-up Value

Short description
Defines the initial power-up value of the motor protection accumulator
Mode
Open‑loop
Minimum
0
Default
0
Type
8 Bit User Save
Display Format
Standard
Coding
RW, TE
Value
Text
0
Pr.dn
1
0
2
Real t
See Motor Thermal Time Constant 1 (04.015).
Parameter

04.041 User Over Current Trip Level

Short description
Defines the trip level for the user over-current trip as a percentage of the drive over current trip level.
Mode
Open‑loop
Minimum
0
Default
100
Type
8 Bit User Save
Display Format
Standard
Coding
RW, RA
The User Over-Current Trip protection level in % of Full Scale Current Kc (11.061) which is the full scale current in r.m.s. Amps. The User Over-Current
Trip may be used to limit the output current of the drive when supplying a motor with a lower current rating than the drive. If the value
of User Over Current Trip Level (04.041) is set at 100%, the user over-current trip is disabled.
Unidrive M200 Parameter Reference Guide
Issue: 01.05.00.10
Maximum
1
Units
Update Rate
Background read
Decimal Places
0
Maximum
VM_USER_CURRENT
Units
%
Update Rate
Background read
Decimal Places
1
Maximum
2
Units
Update Rate
Background write
Decimal Places
0
Maximum
100
Units
%
Update Rate
Background read
Decimal Places
0
61