Low AC Alarm (10.107) is displayed from step 2 on the figure above.
The functionality described for Low DC Link Operation (06.077) is supported across Frames 02-09. For Frames 05 and above, the minimum supply voltage supported is 330V DC (233VAC
RMS)
Parameter

06.084 UTC Offset

Short description
UTC Offset
Mode
Open‑loop
Minimum
-24.00
Default
0.00
Type
16 Bit User Save
Display Format
Standard
Coding
RW
UTC Offset (06.084) is an offset, specified in hours, applied to the selected clock source (see Date/Time Selector  (06.019)). This could be used for time zone offsets etc. The offset will be
applied to the time obtained from the selected clock source, in addition to any offset already applied to the time from that source.
Parameter

06.089 DC Injection Active

Short description
Indicates when d.c. injection is active.
Mode
Open‑loop
Minimum
0
Default
Type
1 Bit User Save
Display Format
Standard
Coding
RO, ND, NC, PT
This flag is high when the sequencer is in the dc injection state and low for all other conditions.
98
Maximum
24.00
Units
Hours
Update Rate
Background read
Decimal Places
2
Maximum
1
Units
Update Rate
4ms
Decimal Places
0
Unidrive M200 Parameter Reference Guide
Issue: 01.05.00.10

Hide quick links:

Advertisement