Binary Sum Offset; Timer 1 Start Date; Timer 1 Start Time; Timer 1 Stop Date/Timer 1 Stop Time - Emerson Unidrive M200 Parameter Reference Manual

Open-loop mode
Hide thumbs Also See for Unidrive M200:
Table of Contents

Advertisement

Parameter

09.034 Binary Sum Offset

Short description
Defines the offset added to the output of the binary sum
Mode
Open‑loop
Minimum
0
Default
0
Type
8 Bit User Save
Display Format
Standard
Coding
RW, BU
See Binary Sum Output (09.032).
Parameter

09.035 Timer 1 Start Date

Short description
Defines the start date for timer 1
Mode
Open‑loop
0
Minimum
(Display: 00-00-00)
0
Default
(Display: 00-00-00)
Type
32 Bit User Save
Display Format
Date
Coding
RW
Timer 1 Start Date (09.035) defines the start date within the repeat period of timer 1.
See Timer 1 Repeat Function (09.039) for more information.
Parameter

09.036 Timer 1 Start Time

Short description
Defines the start time for timer 1
Mode
Open‑loop
0
Minimum
(Display: 00:00:00)
0
Default
(Display: 00:00:00)
Type
32 Bit User Save
Display Format
Time
Coding
RW
Timer 1 Start Time (09.036) defines the start time within the repeat period of timer 1.
See Timer 1 Repeat Function (09.039) for more information.
Parameter
09.037 Timer 1 Stop Date
Short description
Defines the stop date for timer 1
Mode
Open‑loop
0
Minimum
(Display: 00-00-00)
0
Default
(Display: 00-00-00)
Type
32 Bit User Save
Display Format
Date
Coding
RW
Timer 1 Stop Date (09.037) defines the stop date within the repeat period of timer 1.
See Timer 1 Repeat Function (09.039) for more information.
Parameter
09.038 Timer 1 Stop Time
Short description
Defines the stop time for timer 1
Mode
Open‑loop
0
Minimum
(Display: 00:00:00)
0
Default
(Display: 00:00:00)
Type
32 Bit User Save
Display Format
Time
Coding
RW
Timer 1 Stop Time (09.038) defines the stop time within the repeat period of timer 1.
See Timer 1 Repeat Function (09.039) for more information.
136
Maximum
248
Units
Update Rate
4ms read
Decimal Places
0
311299
Maximum
(Display: 31-12-99)
Units
Update Rate
Background read
Decimal Places
0
235959
Maximum
(Display: 23:59:59)
Units
Update Rate
Background read
Decimal Places
0
311299
Maximum
(Display: 31-12-99)
Units
Update Rate
Background read
Decimal Places
0
235959
Maximum
(Display: 23:59:59)
Units
Update Rate
Background read
Decimal Places
0
Unidrive M200 Parameter Reference Guide
Issue: 01.05.00.10

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents