Drive Date Code; Onboard User Program: Clock Task Schedule Rate; Maximum Rated Current; Full Scale Current Kc/Product Type - Emerson Unidrive M200 Parameter Reference Manual
Drive Date Code (11.054) is a four-digit number in the form yyww where yy is the year and ww is the week.
Parameter
11.055 Onboard User Program: Clock Task Schedule Rate
Short description
Displays the interval at which the clock task is scheduled in ms
Mode
Open‑loop
Minimum
0
Default
Type
32 Bit Volatile
Display Format
Standard
Coding
RO, ND, NC, PT
Onboard User Program: Clock Task Schedule Rate (11.055) shows the rate at which the timed task is scheduled in ms.
Parameter
11.060 Maximum Rated Current
Short description
Displays the maximum rated current or normal duty rating of the drive
Mode
Open‑loop
Minimum
0.000
Default
Type
32 Bit Volatile
Display Format
Standard
Coding
RO, ND, NC, PT
Maximum Rated Current (11.060) defines the variable maximum VM_RATED_CURRENT[MAX] which in turn limits the maximum Motor Rated Current
(05.007). Therefore Maximum Maximum Rated Current (11.060) is the maximum rated current for normal duty operation (if normal duty operation is
allowed); or the maximum continuous rating of the drive.
Parameter
11.061 Full Scale Current Kc
Short description
Displays the full scale current Kc
Mode
Open‑loop
Minimum
0.000
Default
Type
32 Bit Volatile
Display Format
Standard
Coding
RO, ND, NC, PT
Full Scale Current Kc (11.061) shows the full scale current in r.m.s. Amps. If the drive current exceeds this level it will cause an over-current trip.
Parameter
11.063 Product Type
Short description
Displays the core product type
Mode
Open‑loop
Minimum
0
Default
Type
8 Bit Volatile
Display Format
Standard
Coding
RO, ND, NC, PT, BU
Product Type (11.063) shows the core product type as given in the table below. The drive could be the basic product or a derivative of the basic product