Parameter

04.007 Symmetrical Current Limit

Short description
Defines the symmetrical current limit
Mode
Open‑loop
Minimum
−VM_MOTOR1_CURRENT_LIMIT
Default
165.0
Type
16 Bit User Save
Display Format
Standard
Coding
RW, VM, RA
See Motoring Current Limit (04.005).
Parameter
04.008 Torque Reference
Short description
Defines the torque reference
Mode
Open‑loop
Minimum
−VM_USER_CURRENT
Default
0.0
Type
32 Bit User Save
Display Format
Standard
Coding
RW, VM
See Final Torque Reference (04.003).
Parameter
04.011 Torque Mode Selector
Short description
Defines the torque mode used by the drive
Mode
Open‑loop
Minimum
0
Default
0
Type
8 Bit User Save
Display Format
Standard
Coding
RW
If Torque Mode Selector (04.011) = 0 the ramp system defines the Post Ramp Reference (02.001) unless the current limits are active, and so the motor
is frequency controlled. If Torque Mode Selector (04.011) = 1 the torque controller defines the Post Ramp Reference (02.001), and so the motor is
torque controlled.
Parameter
04.013 Current Controller Kp Gain
Short description
Defines the current loop controller proportional gain
Mode
Open‑loop
Minimum
0.00
Default
20.00
Type
32 Bit User Save
Display Format
Standard
Coding
RW
Current Controller Kp Gain (04.013) and Current Controller Ki Gain (04.014) are the proportional and integral gains of the current controller.
Refer to Torque and current control .
Parameter
04.014 Current Controller Ki Gain
Short description
Defines the current loop controller integral gain
Mode
Open‑loop
Minimum
0.000
Default
40.000
Type
32 Bit User Save
Display Format
Standard
Coding
RW
See Current Controller Kp Gain (04.013).
Parameter

04.015 Motor Thermal Time Constant 1

Short description
Set to the thermal time constant for the motor
Mode
Open‑loop
Minimum
1
Default
179
Type
16 Bit User Save
Display Format
Standard
Coding
RW
A single time constant thermal model is provided that can be used to estimate the motor temperature as a percentage of its maximum allowed
temperature. The input to the model is the Current Magnitude (04.001). Throughout the following discussion Motor Rated Current (05.007) is used in the
56
Maximum
VM_MOTOR1_CURRENT_LIMIT
Units
%
Update Rate
16ms
Decimal Places
1
Maximum
VM_USER_CURRENT
Units
%
Update Rate
1ms
Decimal Places
1
Maximum
1
Units
Update Rate
16ms
Decimal Places
0
Maximum
4000.00
Units
Update Rate
Background read
Decimal Places
2
Maximum
600.000
Units
Update Rate
Background read
Decimal Places
3
Maximum
3000
Units
s
Update Rate
Background read
Decimal Places
0
Unidrive M200 Parameter Reference Guide