Direct Remote Trip And Transmission Of Binary Information - Siemens siprotec 7SD5 User Manual

Line differential protection with distance protection
Hide thumbs Also See for siprotec 7SD5:
Table of Contents

Advertisement

4.12

Direct Remote Trip and Transmission of Binary Information

Remote Commands
Number of possible remote commands
The operating times depend on the number of ends and the communication speed. The following data presuppose
a transmission speed of 512 kBit/s and the output of commands via high-speed output relays (7SD5****-
*N/P/Q/R/S/T).
The operating times refer to the entire signal path from entry via binary inputs until output of commands via output
relays.
Operating times, total approx.
For 2 ends
For 3 ends
For 6 ends
Dropout times, total approx.
For 2 ends
For 3 ends
For 6 ends
Remote Indications
Number of possible remote commands
The operating times depend on the number of ends and the communication speed. The following data presuppose
a transmission speed of 512 kBit/s and the output of commands via high-speed output relays (7SD5****-
*N/P/Q/R/S/T).
The operating times refer to the entire signal path from entry via binary inputs until output of commands via output
relays.
Operating times, total approx.
for 2 ends
for 3 ends
for 6 ends
Drop-off times, total approx.
for 2 ends
for 3 ends
for 6 ends
7SD5 Manual
C53000-G1176-C169-1
4.12 Direct Remote Trip and Transmission of Binary Information
minimum
typical
minimum
typical
minimum
typical
typical
typical
typical
minimum
typical
minimum
typical
minimum
typical
typical
typical
typical
4
8 ms
12 ms
10 ms
14 ms
15 ms
18 ms
19 ms
20 ms
26 ms
24
9 ms
16 ms
12 ms
18 ms
17 ms
23 ms
24 ms
25 ms
32 ms
553

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents