Line differential protection with distance protection
Hide thumbs Also See for siprotec 7SD5:
Table of Contents

Advertisement

2 Functions
Switching onto a
To perform an instantaneous trip when the circuit breaker is manually closed onto a
Fault
dead fault, the manual closing command of the control discrepancy switch can be fed
to the device via a binary input. The overcurrent protection can then trip three-pole
without delay or with a reduced delay. It can be determined via parameter setting for
which stage(s) the rapid tripping following manually closure on to a dead fault applies
(refer also to the logic Figures 2-117, 2-118 and 2-119).
Pickup and Trip-
The pickup signals of the individual phases (or the earth) and of the stages are linked
ping Logic
in such a way that both the phase information and the stage which has picked up are
indicated (Table 2-12).
In case of trip signals, the stage which resulted in the trip command is also indicated.
For single-pole tripping, the pole is identified (see also Section 2.23.1 „Pickup Logic of
the Entire Device").
Table 2-12
274
Pickup signals of the single phases
Internal Indication
I>> PU L1
I> PU L1
Ip PU L1
I>>> PU L1
I>> PU L2
I> PU L2
Ip PU L2
I>>> PU L2
I>> PU L3
I> PU L3
Ip PU L3
I>>> PU L3
I>> PU E
I> PU E
Ip PU E
I>>> PU E
I>> PU L1
I>> PU L2
I>> PU L3
I>> PU E
I> PU L1
I> PU L2
I> PU L3
I> PU E
Ip PU L1
Ip PU L2
Ip PU L3
Ip PU E
I>>> PU L1
I>>> PU L2
I>>> PU L3
I>>> PU E
(All pickups)
Display
Output Indication
2-117
„O/C Pickup L1"
2-118
2-119
2-117
„O/C Pickup L2"
2-118
2-119
2-117
„O/C Pickup L3"
2-118
2-119
2-117
„O/C Pickup E"
2-118
2-119
2-117
2-117
„O/C PICKUP I>>"
2-117
2-117
„O/C PICKUP I>"
2-118
2-118
„O/C PICKUP Ip"
2-118
2-118
2-119
2-119
„I-STUB PICKUP"
2-119
2-119
„O/C PICKUP"
No.
7162
7163
7164
7165
7191
7192
7193
7201
7161
7SD5 Manual