Siemens siprotec 7SD5 User Manual page 631

Line differential protection with distance protection
Hide thumbs Also See for siprotec 7SD5:
Table of Contents

Advertisement

Addr.
Parameter
3426
AR w/ W/I
3427
AR w/ EF-O/C
3430
AR TRIP 3pole
3431
DLC / RDT
3433
T-ACTION ADT
3434
T-MAX ADT
3435
ADT 1p allowed
3436
ADT CB? CLOSE
3437
ADT SynRequest
3438
T U-stable
3440
U-live>
3441
U-dead<
3450
1.AR: START
3451
1.AR: T-ACTION
3453
1.AR Tdead 1Flt
3454
1.AR Tdead 2Flt
3455
1.AR Tdead 3Flt
3456
1.AR Tdead1Trip
3457
1.AR Tdead3Trip
3458
1.AR: Tdead EV.
3459
1.AR: CB? CLOSE
3460
1.AR SynRequest
3461
2.AR: START
3462
2.AR: T-ACTION
3464
2.AR Tdead 1Flt
3465
2.AR Tdead 2Flt
3466
2.AR Tdead 3Flt
3467
2.AR Tdead1Trip
3468
2.AR Tdead3Trip
3469
2.AR: Tdead EV.
3470
2.AR: CB? CLOSE
3471
2.AR SynRequest
3472
3.AR: START
3473
3.AR: T-ACTION
3475
3.AR Tdead 1Flt
3476
3.AR Tdead 2Flt
3477
3.AR Tdead 3Flt
3478
3.AR Tdead1Trip
3479
3.AR Tdead3Trip
3480
3.AR: Tdead EV.
3481
3.AR: CB? CLOSE
3482
3.AR SynRequest
7SD5 Manual
C53000-G1176-C169-1
Function
C
Setting Options
Auto Reclose
YES
NO
Auto Reclose
YES
NO
Auto Reclose
YES
NO
Auto Reclose
WITHOUT
DLC
0.01 .. 300.00 sec; ∞
Auto Reclose
Auto Reclose
0.50 .. 3000.00 sec
Auto Reclose
YES
NO
Auto Reclose
YES
NO
Auto Reclose
YES
NO
Auto Reclose
0.10 .. 30.00 sec
Auto Reclose
30 .. 90 V
Auto Reclose
2 .. 70 V
Auto Reclose
YES
NO
0.01 .. 300.00 sec; ∞
Auto Reclose
0.01 .. 1800.00 sec; ∞
Auto Reclose
0.01 .. 1800.00 sec; ∞
Auto Reclose
0.01 .. 1800.00 sec; ∞
Auto Reclose
0.01 .. 1800.00 sec; ∞
Auto Reclose
0.01 .. 1800.00 sec; ∞
Auto Reclose
Auto Reclose
0.01 .. 1800.00 sec
Auto Reclose
YES
NO
Auto Reclose
YES
NO
Auto Reclose
YES
NO
0.01 .. 300.00 sec; ∞
Auto Reclose
0.01 .. 1800.00 sec; ∞
Auto Reclose
0.01 .. 1800.00 sec; ∞
Auto Reclose
0.01 .. 1800.00 sec; ∞
Auto Reclose
0.01 .. 1800.00 sec; ∞
Auto Reclose
0.01 .. 1800.00 sec; ∞
Auto Reclose
Auto Reclose
0.01 .. 1800.00 sec
Auto Reclose
YES
NO
Auto Reclose
YES
NO
Auto Reclose
YES
NO
0.01 .. 300.00 sec; ∞
Auto Reclose
0.01 .. 1800.00 sec; ∞
Auto Reclose
0.01 .. 1800.00 sec; ∞
Auto Reclose
0.01 .. 1800.00 sec; ∞
Auto Reclose
0.01 .. 1800.00 sec; ∞
Auto Reclose
0.01 .. 1800.00 sec; ∞
Auto Reclose
Auto Reclose
0.01 .. 1800.00 sec
Auto Reclose
YES
NO
Auto Reclose
YES
NO
Default Setting
YES
AR with weak infeed tripping ?
YES
AR with earth fault overcurrent
prot. ?
YES
3pole TRIP by AR
WITHOUT
Dead Line Check / Reduced
Dead Time
0.20 sec
Action time
5.00 sec
Maximum dead time
NO
1pole TRIP allowed
NO
CB ready interrogation before re-
closing
NO
Request for synchro-check after
3pole AR
0.10 sec
Supervision time for dead/live
voltage
48 V
Voltage threshold for live line or
bus
30 V
Voltage threshold for dead line or
bus
YES
Start of AR allowed in this cycle
0.20 sec
Action time
1.20 sec
Dead time after 1phase faults
1.20 sec
Dead time after 2phase faults
0.50 sec
Dead time after 3phase faults
1.20 sec
Dead time after 1pole trip
0.50 sec
Dead time after 3pole trip
1.20 sec
Dead time after evolving fault
NO
CB ready interrogation before re-
closing
NO
Request for synchro-check after
3pole AR
NO
AR start allowed in this cycle
0.20 sec
Action time
1.20 sec
Dead time after 1phase faults
1.20 sec
Dead time after 2phase faults
0.50 sec
Dead time after 3phase faults
∞ sec
Dead time after 1pole trip
0.50 sec
Dead time after 3pole trip
1.20 sec
Dead time after evolving fault
NO
CB ready interrogation before re-
closing
NO
Request for synchro-check after
3pole AR
NO
AR start allowed in this cycle
0.20 sec
Action time
1.20 sec
Dead time after 1phase faults
1.20 sec
Dead time after 2phase faults
0.50 sec
Dead time after 3phase faults
∞ sec
Dead time after 1pole trip
0.50 sec
Dead time after 3pole trip
1.20 sec
Dead time after evolving fault
NO
CB ready interrogation before re-
closing
NO
Request for synchro-check after
3pole AR
A.7 Settings
Comments
631