Line differential protection with distance protection
Hide thumbs Also See for siprotec 7SD5:
Table of Contents

Advertisement

2 Functions
Note
For double-ended fault locating, the devices at the ends must be configured with the
same data, i.e. if there is more than one line section, the values configured for device
B must mirror the data of device A. This means for two line types that line section 1
and 2 configured for device A must be line section 2 and 1 of device B.
If the devices are correctly configured, indication no. 1111 „FL active" will be output
as ON.
If address 160 is set to 2 Sections or 3 Sections, the line impedance angle of
the first line section must be set at address 6001 S1: Line angle, the reactance
per unit length at address 6002 S1: x', and the capacitance per unit length at
address 6003 S1: c'. The line section length is entered at address 6004 S1: Line
length. All values refer to kilometer as distance measuring unit. If you want to use
miles as reference values, the addresses relevant for you are 6002, 6003 and 6004.
The central phase of your transmission tower layout is specified at address 6008 S1:
center ph.. Setting 6008 = unknown/sym. assumes a symmetrical layout.
Line sections 2 (A2) and 3 (A3) are configured in the same way as described above.
For setting values please refer to Table 2-15.
Table 2-15
Additional line section parameters
Addr.
Setting Title
6001
S1: Line angle
6002
S1: x'
6003
S1: c'
6004
S1: Line length
6008
S1: center ph.
6021
S2: Line angle
6022
S2: x'
354
C
Setting Options
30-89 °; ohne 0
0.0010-1.9000 Ω/km; ohne
1 A
0
0.0050-9.5000 Ω/km;
5 A
without 0
0.0010-3.0000 Ω/mi; ohne
1 A
0
0.0050-15.0000 Ω/mile;
5 A
without 0
0.000-500.000 µF/km; 0
1 A
0.000-100.000 µF/km; 0
5 A
0.000-800.000 µF/mi; 0
1 A
0.000-160.000 µF/mile; 0
5 A
0.1-1000.0 km; ohne 0
0.1-650.0 Miles; ohne 0
unknown/sym.
Phase 1
Phase 2
Phase 3
30-89 °; ohne 0
0.0010-1.9000 Ω/km; ohne
1 A
0
0.0050-9.5000 Ω/km;
5 A
without 0
0.0010-3.0000 Ω/mi; ohne
1 A
0
0.0050-15.0000 Ω/mile;
5 A
without 0
Default Settings
85 °
A1: Line impedance angle
0.0300 Ω/km
A1: Line reactance per unit
length: x' in Ω/km
0.1500 Ω/km
0.0484 Ω/mi
A1: Line reactance per unit
length: x' in Ω/mile
0.2420 Ω/mile
0.050 µF/km
A1: Capacitance per unit
length C' in µF/km
0.010 µF/km
0.080 µF/mi
A1: Capacitance per unit
length C' in µF/mile
0.016 µF/mile
100.0 km
A1: Line length in kilome-
ters
62.1 Miles
A1: Line length in miles
unknown/sym.
A1: Central phase
85 °
A2: Line impedance angle
0.0300 Ω/km
A2: Line reactance per unit
length: x' in Ω/km
0.1500 Ω/km
0.0484 Ω/mi
A2: Line reactance per unit
length: x' in Ω/mile
0.2420 Ω/mile