block is to be activated is set under address 2310 CROSSB 2HM. With the setting ∞
the crossblock function is always active until the second harmonic content in all
phases has dropped below the set value.
2.3.3

Settings

Addresses which have an appended "A" can only be changed with DIGSI, under Ad-
ditional Settings.
The table indicates region-specific presettings. Column C (configuration) indicates the
corresponding secondary nominal current of the current transformer.
Addr.
Parameter
1201
STATE OF DIFF.
1210
I-DIFF>
1213
I-DIF>SWITCH ON
1217A
T-DELAY I-DIFF>
1218
T3I0 1PHAS
1221
Ic-comp.
1224
IcSTAB/IcN
1233
I-DIFF>>
2301
INRUSH REST.
2302
2nd HARMONIC
2303
CROSS BLOCK
2305
MAX INRUSH PEAK
2310
CROSSB 2HM
7SD5 Manual
C53000-G1176-C169-1
C
Setting Options
OFF
ON
1A
0.10 .. 20.00 A
5A
0.50 .. 100.00 A
1A
0.10 .. 20.00 A
5A
0.50 .. 100.00 A
0.00 .. 60.00 sec; ∞
0.00 .. 0.50 sec; ∞
OFF
ON
2.0 .. 4.0
0.8 .. 100.0 A; ∞
1A
4.0 .. 500.0 A; ∞
5A
OFF
ON
10 .. 45 %
NO
YES
1A
1.1 .. 25.0 A
5A
5.5 .. 125.0 A
0.00 .. 60.00 sec; ∞
2.3 Differential Protection
Default Setting
ON
State of differential protec-
tion
0.30 A
I-DIFF>: Pickup value
1.50 A
0.30 A
I-DIFF>: Value under
switch on condition
1.50 A
0.00 sec
I-DIFF>: Trip time delay
0.04 sec
Delay 1ph-faults
(comp/isol. star-point)
OFF
Charging current compen-
sation
2.5
Ic Stabilising / Ic Nominal
1.2 A
I-DIFF>>: Pickup value
6.0 A
OFF
Inrush Restraint
15 %
2nd. harmonic in % of fun-
damental
NO
Cross Block
15.0 A
Maximum inrush-peak
value
75.0 A
0.00 sec
Time for Crossblock with
2nd harmonic
Comments