3 Mounting and Commissioning
WARNING!
Warning of dangers evolving from improper primary tests
Non-observance of the following measure can result in death, personal injury or sub-
stantial property damage.
Primary tests may only be carried out by qualified persons who are familiar with com-
missioning protection systems, with managing power systems and the relevant safety
rules and guidelines (switching, earthing etc.).
3.3.1

Test Mode / Transmission Block

Activation and
If the device is connected to a central control system or a server via the SCADA inter-
Deactivation
face, then the information that is transmitted can be modified with some of the proto-
cols available (see Table „Protocol-dependent functions" in the Appendix A.5).
If Test mode is set ON, then a message sent by a SIPROTEC
control system has an additional test bit. This bit allows the message to be recognized
as resulting from testing and not an actual fault or power system event. Furthermore,
it can be determined by activating the Transmission block that no annunciations at
all are transmitted via the system interface during a test mode.
The SIPROTEC
mode and blocked data transmission. Note that when DIGSI
program must be in the Online operating mode for the test features to be used.
3.3.2

Checking the Time Synchronization Interface

If external time synchronization sources are used, the data of the time source (antenna
system, time generator) are checked (see Section 4 under „Time Synchronization"). A
correct function (IRIG B, DCF77) is recognized in such a way that 3 minutes after the
startup of the device the clock status is displayed as „sychronized", accompanied
by the indication „Alarm Clock OFF".
Table 3-14
478
®
4 System Description describes how to activate and deactivate test
Time status
No.
1
– – – – – – – –
2
– – – – – – ST
3
– – – – ER – –
4
– – – – ER ST
5
– – NS ER – –
6
– – NS – – – –
Legend:
– – NS – – – –
– – – – ER – –
– – – – – – ST
Status text
synchronized
not synchronized
time invalid
time fault
summertime
®
4 device to the main
®
is being used, the
Status
7SD5 Manual
C53000-G1176-C169-1