2 Functions
2.6.2

Setting Notes

The power swing supplement is only active if it has been set to Power Swing =
Enabled (address 120) during the configuration. For Power Swing no other param-
eters have to be set.
The four possible programs may be set in address 2002 P/S Op. mode, as de-
scribed in Section 2.6: All zones block, Z1/Z1B block, Z2 to Z5 block or
Z1,Z1B,Z2 block.
Additionally the tripping function for unstable oscillations (out-of-step condition, loss of
system synchronism) can be set with parameter PowerSwing trip (address 2006),
which should be set to YES if required (presetting is NO). In the event of power swing
tripping it is recommended to set P/S Op. mode = All zones block for the power
swing blocking, to avoid premature tripping by the distance protection.
The tripping delay after power swing blocking can be set in address 2007 Trip
DELAY P/S.
2.6.3

Settings

Addr.
Parameter
2002
P/S Op. mode
2006
PowerSwing trip
2007
Trip DELAY P/S
2.6.4

Information List

No.
Information
4160
>Pow. Swing BLK
4163
P.Swing unstab.
4164
Power Swing
4166
Pow. Swing TRIP
4167
Pow. Swing L1
4168
Pow. Swing L2
4169
Pow. Swing L3
174
Setting Options
All zones block
Z1/Z1B block
Z2 to Z5 block
Z1,Z1B,Z2 block
NO
YES
0.08 .. 5.00 sec; 0
Type of In-
formation
SP
>BLOCK Power Swing detection
OUT
Power Swing unstable
OUT
Power Swing detected
OUT
Power Swing TRIP command
OUT
Power Swing detected in L1
OUT
Power Swing detected in L2
OUT
Power Swing detected in L3
Default Setting
All zones block
Power Swing Operating mode
NO
Power swing trip
0.08 sec
Trip delay after Power Swing
Blocking
Comments
Comments
7SD5 Manual