Siemens siprotec 7SD5 User Manual page 623

Line differential protection with distance protection
Hide thumbs Also See for siprotec 7SD5:
Table of Contents

Advertisement

Addr.
Parameter
1612
R(Z2) Ø-Ø
1613
X(Z2)
1614
RE(Z2) Ø-E
1615
T2-1phase
1616
T2-multi-phase
1617A
Trip 1pole Z2
1621
Op. mode Z3
1622
R(Z3) Ø-Ø
1623
X(Z3)
1624
RE(Z3) Ø-E
1625
T3 DELAY
1631
Op. mode Z4
1632
R(Z4) Ø-Ø
1633
X(Z4)
1634
RE(Z4) Ø-E
1635
T4 DELAY
1641
Op. mode Z5
1642
R(Z5) Ø-Ø
1643
X(Z5)+
1644
RE(Z5) Ø-E
1645
T5 DELAY
1646
X(Z5)-
1651
Op. mode Z1B
1652
R(Z1B) Ø-Ø
7SD5 Manual
C53000-G1176-C169-1
Function
C
Setting Options
0.050 .. 600.000 Ω
Dis. Quadril.
1A
0.010 .. 120.000 Ω
5A
0.050 .. 600.000 Ω
Dis. Quadril.
1A
0.010 .. 120.000 Ω
5A
0.050 .. 600.000 Ω
Dis. Quadril.
1A
0.010 .. 120.000 Ω
5A
0.00 .. 30.00 sec; ∞
Dis. General
Dis. Quadril.
Dis. MHO
0.00 .. 30.00 sec; ∞
Dis. General
Dis. Quadril.
Dis. MHO
Dis. General
NO
Dis. Quadril.
YES
Dis. MHO
Dis. Quadril.
Forward
Reverse
Non-Directional
Inactive
0.050 .. 600.000 Ω
Dis. Quadril.
1A
0.010 .. 120.000 Ω
5A
0.050 .. 600.000 Ω
Dis. Quadril.
1A
0.010 .. 120.000 Ω
5A
0.050 .. 600.000 Ω
Dis. Quadril.
1A
0.010 .. 120.000 Ω
5A
0.00 .. 30.00 sec; ∞
Dis. General
Dis. Quadril.
Dis. MHO
Dis. Quadril.
Forward
Reverse
Non-Directional
Inactive
0.050 .. 600.000 Ω
Dis. Quadril.
1A
0.010 .. 120.000 Ω
5A
0.050 .. 600.000 Ω
Dis. Quadril.
1A
0.010 .. 120.000 Ω
5A
0.050 .. 250.000 Ω
Dis. Quadril.
1A
0.010 .. 50.000 Ω
5A
0.00 .. 30.00 sec; ∞
Dis. General
Dis. Quadril.
Dis. MHO
Dis. Quadril.
Forward
Reverse
Non-Directional
Inactive
0.050 .. 600.000 Ω
Dis. Quadril.
1A
0.010 .. 120.000 Ω
5A
0.050 .. 600.000 Ω
Dis. Quadril.
1A
0.010 .. 120.000 Ω
5A
0.050 .. 600.000 Ω
Dis. Quadril.
1A
0.010 .. 120.000 Ω
5A
0.00 .. 30.00 sec; ∞
Dis. General
Dis. Quadril.
Dis. MHO
0.050 .. 600.000 Ω
Dis. Quadril.
1A
0.010 .. 120.000 Ω
5A
Dis. Quadril.
Forward
Reverse
Non-Directional
Inactive
0.050 .. 600.000 Ω
Dis. Quadril.
1A
0.010 .. 120.000 Ω
5A
Default Setting
2.500 Ω
R(Z2), Resistance for ph-ph-
faults
0.500 Ω
5.000 Ω
X(Z2), Reactance
1.000 Ω
5.000 Ω
RE(Z2), Resistance for ph-e
faults
1.000 Ω
0.30 sec
T2-1phase, delay for single
phase faults
0.30 sec
T2multi-ph, delay for multi phase
faults
NO
Single pole trip for faults in Z2
Reverse
Operating mode Z3
5.000 Ω
R(Z3), Resistance for ph-ph-
faults
1.000 Ω
10.000 Ω
X(Z3), Reactance
2.000 Ω
10.000 Ω
RE(Z3), Resistance for ph-e
faults
2.000 Ω
0.60 sec
T3 delay
Non-Directional
Operating mode Z4
12.000 Ω
R(Z4), Resistance for ph-ph-
faults
2.400 Ω
12.000 Ω
X(Z4), Reactance
2.400 Ω
12.000 Ω
RE(Z4), Resistance for ph-e
faults
2.400 Ω
0.90 sec
T4 delay
Inactive
Operating mode Z5
12.000 Ω
R(Z5), Resistance for ph-ph-
faults
2.400 Ω
12.000 Ω
X(Z5)+, Reactance for Forward
direction
2.400 Ω
12.000 Ω
RE(Z5), Resistance for ph-e
faults
2.400 Ω
0.90 sec
T5 delay
4.000 Ω
X(Z5)-, Reactance for Reverse
direction
0.800 Ω
Forward
Operating mode Z1B (overrreach
zone)
1.500 Ω
R(Z1B), Resistance for ph-ph-
faults
0.300 Ω
A.7 Settings