Chapter 1) 7SR23 DAD Description Of Operation
2.7

Binary inputs

The binary inputs are isolated with opto-couplers and can be operated from a suitably rated dc supply.
Relays are fitted with 9 or 19 binary inputs (BI). The user can assign any binary input to any of the available
functions (INPUT CONFIG > INPUT MATRIX).
The Power Supply module includes the relay basic I/O. The module includes 3 x BI.
Pick-up (PU) and drop-off (DO) time delays are associated with each binary input. Where no pick-up time delay
has been applied the input may pick up due to induced ac voltage on the wiring connections (e.g. cross site
wiring). The default pick-up time of 20ms provides ac immunity. Each input can be programmed independently.
Each input may be logically inverted to facilitate integration of the relay within the user scheme. When inverted the
relay indicates that the BI is energised when no d.c. is applied. Inversion occurs before the PU & DO time delay,
see Figure 2-2.
Each input may be mapped to any front Fascia indication LED and/or to any Binary output contact and can also
be used with the internal user programmable logic. This allows the relay to provide panel indications and alarms.
Figure 2-2
Binary Input Logic
©2013 Siemens Protection Devices Limited