Siemens siprotec 7SD5 User Manual page 629

Line differential protection with distance protection
Hide thumbs Also See for siprotec 7SD5:
Table of Contents

Advertisement

Addr.
Parameter
3140
Op. mode 3I0p
3141
3I0p PICKUP
3141
3I0p PICKUP
3142
3I0p MinT-DELAY
3143
3I0p Time Dial
3144
3I0p Time Dial
3145
3I0p Time Dial
3146
3I0p MaxT-DELAY
3147
Add.T-DELAY
3148
3I0p Telep/BI
3149
3I0p SOTF-Trip
3150
3I0p InrushBlk
3151
IEC Curve
3152
ANSI Curve
3153
LOG Curve
3154
3I0p Startpoint
3155
k
3156
S ref
3160
POLARIZATION
3162A
Dir. ALPHA
3163A
Dir. BETA
3164
3U0>
3165
IY>
3166
3U2>
3167
3I2>
7SD5 Manual
C53000-G1176-C169-1
Function
C
Setting Options
Earth Fault O/C
Forward
Earth Fault O/C
Reverse
Earth Fault O/C
Non-Directional
Earth Fault O/C
Inactive
Earth Fault O/C
1A
0.05 .. 25.00 A
Earth Fault O/C
5A
0.25 .. 125.00 A
Earth Fault O/C
Earth Fault O/C
Earth Fault O/C
1A
0.003 .. 25.000 A
Earth Fault O/C
5A
0.015 .. 125.000 A
Earth Fault O/C
Earth Fault O/C
Earth Fault O/C
0.00 .. 30.00 sec
0.05 .. 3.00 sec; ∞
Earth Fault O/C
0.50 .. 15.00 ; ∞
Earth Fault O/C
0.05 .. 15.00 sec; ∞
Earth Fault O/C
Earth Fault O/C
0.00 .. 30.00 sec
0.00 .. 30.00 sec; ∞
Earth Fault O/C
Earth Fault O/C
Earth Fault O/C
Earth Fault O/C
Earth Fault O/C
NO
Earth Fault O/C
YES
Earth Fault O/C
Earth Fault O/C
Earth Fault O/C
NO
Earth Fault O/C
YES
Earth Fault O/C
Earth Fault O/C
Earth Fault O/C
NO
Earth Fault O/C
YES
Earth Fault O/C
Earth Fault O/C
Earth Fault O/C
Normal Inverse
Very Inverse
Extremely Inv.
LongTimeInverse
Earth Fault O/C
Inverse
Short Inverse
Long Inverse
Moderately Inv.
Very Inverse
Extremely Inv.
Definite Inv.
Earth Fault O/C
Log. inverse
Earth Fault O/C
1.0 .. 4.0
Earth Fault O/C
0.00 .. 3.00 sec
Earth Fault O/C
1A
1 .. 100 VA
5A
5 .. 500 VA
Earth Fault O/C
U0 + IY or U2
U0 + IY
with IY only
with U2 and I2
zero seq. power
0 .. 360 °
Earth Fault O/C
0 .. 360 °
Earth Fault O/C
Earth Fault O/C
0.5 .. 10.0 V
Earth Fault O/C
1A
0.05 .. 1.00 A
5A
0.25 .. 5.00 A
Earth Fault O/C
0.5 .. 10.0 V
Earth Fault O/C
1A
0.05 .. 1.00 A
5A
0.25 .. 5.00 A
Default Setting
Inactive
Operating mode
1.00 A
3I0p Pickup
5.00 A
1.000 A
3I0p Pickup
5.000 A
1.20 sec
3I0p Minimum Time Delay
0.50 sec
3I0p Time Dial
5.00
3I0p Time Dial
1.35 sec
3I0p Time Dial
5.80 sec
3I0p Maximum Time Delay
1.20 sec
Additional Time Delay
NO
Instantaneous trip via Tele-
prot./BI
NO
Instantaneous trip after Switch-
OnToFault
NO
Inrush Blocking
Normal Inverse
IEC Curve
Inverse
ANSI Curve
Log. inverse
LOGARITHMIC Curve
1.1
Start point of inverse characteris-
tic
0.50 sec
k-factor for Sr-characteristic
10 VA
S ref for Sr-characteristic
50 VA
U0 + IY or U2
Polarization
338 °
ALPHA, lower angle for forward
direction
122 °
BETA, upper angle for forward di-
rection
0.5 V
Min. zero seq.voltage 3U0 for po-
larizing
0.05 A
Min. earth current IY for polariz-
ing
0.25 A
0.5 V
Min. neg. seq. polarizing voltage
3U2
0.05 A
Min. neg. seq. polarizing current
3I2
0.25 A
A.7 Settings
Comments
629