2 Functions
The data can be retrieved via the serial interfaces by means of a personal computer
and evaluated with the operating software DIGSI
SIGRA 4. The latter graphically represents the data recorded during the system fault
and also calculates additional information from the measured values. A selection may
be made as to whether the measured quantities are represented as primary or sec-
ondary values. Binary signal traces (marks) of particular events, e.g. „fault detection",
„tripping" are also represented.
If the device has a serial system interface, the fault recording data can be passed on
to a central device via this interface. The data is evaluated by applicable programs in
the central device. The measured quantities are referred to their maximum values,
scaled to their rated values and prepared for graphic representation. Binary signal
traces (marks) of particular events, e.g. „fault detection", „tripping" are also represent-
ed.
Where transfer to a central device is possible, the request for data transfer can be ex-
ecuted automatically. It can be selected to take place after each fault detection by the
protection, or only after a trip.

2.24.8.2 Settings

Addresses which have an appended "A" can only be changed with DIGSI, under Ad-
ditional Settings.
Addr.
Parameter
402A
WAVEFORMTRIGGE
R
403A
WAVEFORM DATA
410
MAX. LENGTH
411
PRE. TRIG. TIME
412
POST REC. TIME
415
BinIn CAPT.TIME

2.24.8.3 Information List

No.
Information
-
FltRecSta
4
>Trig.Wave.Cap.
203
Wave. deleted
430
Setting Options
Save w. Pickup
Save w. TRIP
Start w. TRIP
Fault event
Pow.Sys.Flt.
0.30 .. 5.00 sec
0.05 .. 0.50 sec
0.05 .. 0.50 sec
0.10 .. 5.00 sec; ∞
Type of In-
formation
IntSP
Fault Recording Start
SP
>Trigger Waveform Capture
OUT_Ev
Waveform data deleted
®
and the graphic analysis software
Default Setting
Save w. Pickup
Waveform Capture
Fault event
Scope of Waveform Data
2.00 sec
Max. length of a Waveform
Capture Record
0.25 sec
Captured Waveform Prior to
Trigger
0.10 sec
Captured Waveform after Event
0.50 sec
Capture Time via Binary Input
Comments
Comments
7SD5 Manual
C53000-G1176-C169-1