Settings - Siemens siprotec 7SD5 User Manual

Line differential protection with distance protection
Hide thumbs Also See for siprotec 7SD5:
Table of Contents

Advertisement

2.1.1.4

Settings

Addr.
Parameter
103
Grp Chge OPTION
110
Trip mode
112
DIFF.PROTECTION
115
Phase Distance
116
Earth Distance
117
Dis. PICKUP
120
Power Swing
121
Teleprot. Dist.
122
DTT Direct Trip
124
HS/SOTF-O/C
125
Weak Infeed
126
Back-Up O/C
131
Earth Fault O/C
132
Teleprot. E/F
7SD5 Manual
C53000-G1176-C169-1
Setting Options
Disabled
Enabled
3pole only
1-/3pole
Enabled
Disabled
Quadrilateral
MHO
Disabled
Quadrilateral
MHO
Disabled
Z< (quadrilat.)
I> (overcurr.)
U/I
U/I/ϕ
Disabled
Disabled
Enabled
PUTT (Z1B)
PUTT (Pickup)
POTT
Dir.Comp.Pickup
UNBLOCKING
BLOCKING
Rev. Interlock
Pilot wire comp
Disabled
Disabled
Enabled
Disabled
Enabled
Disabled
Enabled
Logic no. 2
Disabled
TOC IEC
TOC ANSI
Disabled
TOC IEC
TOC ANSI
TOC Logarithm.
Definite Time
U0 inverse
Sr inverse
Dir.Comp.Pickup
UNBLOCKING
BLOCKING
Disabled
Default Setting
Disabled
Setting Group Change Option
3pole only
Trip mode
Enabled
Differential protection
Quadrilateral
Phase Distance
Quadrilateral
Earth Distance
Z< (quadrilat.)
Distance protection pickup
program
Disabled
Power Swing detection
Disabled
Teleprotection for Distance prot.
Disabled
DTT Direct Transfer Trip
Disabled
Instantaneous HighSpeed/SOTF
Overcurrent
Disabled
Weak Infeed (Trip and/or Echo)
TOC IEC
Backup overcurrent
Disabled
Earth fault overcurrent
Disabled
Teleprotection for Earth fault over-
curr.
2.1 General
Comments
43