Siemens SIPROTEC 7SD80 Manual

Siemens SIPROTEC 7SD80 Manual

Line differential protection communication module dnp 3.0 buss mapping / point list
Hide thumbs Also See for SIPROTEC 7SD80:

Advertisement

SIPROTEC
Line Differential Protection
7SD80
Communication Module
DNP 3.0
Buss Mapping / Point List
C53000-L2040-C347-1
Preface
Contents
Notes to SIPROTEC objects
DNP V3.0 Device Profile
Point lists
Glossary
Index
1
2
3

Advertisement

Table of Contents
loading

Summary of Contents for Siemens SIPROTEC 7SD80

  • Page 1 Preface Contents SIPROTEC Notes to SIPROTEC objects DNP V3.0 Device Profile Line Differential Protection 7SD80 Point lists Communication Module Glossary DNP 3.0 Index Buss Mapping / Point List C53000-L2040-C347-1...
  • Page 2 We reserve the right to make technical improvements without SIPROTEC, SINAUT, SICAM and DIGSI are registered trademarks notice. of Siemens AG. Other designations in this manual might be Document release: 01.00.01 trademarks whose use by third parties for their own purposes Edition 07.2011...
  • Page 3: Preface

    SIPROTEC devices: Manual Contents Order number Line Differential Protection Function, operation, assembly and C53000-G1140-C474-1 SIPROTEC 7SD80 commissioning of the SIPROTEC device 7SD80 DNP 3.0 Communication DNP communication database of the C53000-L1840-A001-03 Database SIPROTEC devices SIPROTEC, 7SD80, Bus mapping DNP 3.0...
  • Page 4 Should further information on the System SIPROTEC 4 be desired or should particular problems arise which are not covered sufficiently for the purchaser's purpose, he matter should be referred to the local Siemens representative. Our Customer Support Center provides a 24-hour service.
  • Page 5 Preface Instructions and Warnings The warnings and notes contained in this manual serve for your own safety and for an appropri- ate lifetime of the device. Please observe them! The following terms are used: DANGER indicates that death, severe personal injury or substantial property damage will result if proper precautions are not taken.
  • Page 6 Preface Typographic and Symbol Conventions The following text formats are used when literal information from the device or to the device appear in the text flow: Parameter names, i.e. designators of configuration or function parameters which may appear word-for-word in the display of the device or on the screen of a personal computer (with opera- tion software DIGSI 4), are marked in bold letters of a monospace type style.
  • Page 7: Table Of Contents

    Contents Preface ................. . 3 Notes to SIPROTEC objects .
  • Page 8 Glossary................29 Index.
  • Page 9: Notes To Siprotec Objects

    Notes to SIPROTEC objects This chapter contains notes for the use and evaluation of certain SIPROTEC objects which are available via DNP3.0 communication. The description of the standard mappings / point lists (refer to chapter 3) contains the pre-allocation of the map- ping files at delivery or first assignment of a mapping in DIGSI 4 to the SIPROTEC device.
  • Page 10: Binary Inputs / Annunciations

    1 Notes to SIPROTEC objects 1.1 Binary Inputs / Annunciations Binary Inputs / Annunciations Note Depending on the device composition and the existing protection packages not all of the indicated binary inputs or protection annunciations (and corresponding DNP points) may be available in the SIPROTEC device 1.1.1 Error with a summary alarm The "Error with a summary alarm"...
  • Page 11: Binary Outputs / Commands

    1 Notes to SIPROTEC objects 1.2 Binary Outputs / Commands Binary Outputs / Commands Note The allocation of the output relays to the switching devices and to the output channels is defined during param- etrization of the SIPROTEC devices. Depending on the device composition there may be less than indicated output relays (and corresponding DNP message points) available in the SIPROTEC device.
  • Page 12: Analog Inputs / Measured Values

    1 Notes to SIPROTEC objects 1.3 Analog Inputs / Measured values Analog Inputs / Measured values Note Depending on the device composition not all of the indicated analog inputs (and corresponding DNP message points) may be available in the SIPROTEC device. The given scaling values for the measured values in the standard mapping apply to installations with the fol- lowing nominal operating values: Measurement: Full Scale Voltage (parameter address 1103):...
  • Page 13: Metered Measurands

    1 Notes to SIPROTEC objects 1.4 Metered measurands Metered measurands Scaling The scaling of the metered measurands, which are derived from measured values, refers to: 60000 impulses per hour for V = Vprim and I = Iprim =Full Scale Voltage prim (parameter address = 1103) CALE...
  • Page 14 1 Notes to SIPROTEC objects 1.4 Metered measurands SIPROTEC, 7SD80, Bus mapping DNP 3.0 C53000-L2040-C347-1, Edition 07.2011...
  • Page 15: Dnp V3.0 Device Profile

    DNP V3.0 Device Profile Implementation Table 2-16 Device Profile Document 2-18 SIPROTEC, 7SD80, Bus mapping DNP 3.0 C53000-L2040-C347-1, Edition 07.2011...
  • Page 16: Implementation Table

    DNP V3.0 Device Profile 2.1 Implementation Table Implementation Table The following table gives a list of all objects recognized and returned by the SIPROTEC device. For static objects, requests sent with qualifiers 00, 01, 06, 07 or 08 will be responded with qualifiers 00 or 01.
  • Page 17 DNP V3.0 Device Profile 2.1 Implementation Table OBJECTS REQUEST RESPONSE Object Vari- Description Function Qualifier Codes Function Qualifier Codes ation Codes (hex) Codes (dec) (hex) (dec) 16-Bit Analog Input - 00, 01 (read) (start-stop) (no range) Any Variations 07, 08 (limited qfy) 17, 28 (index)
  • Page 18: Device Profile Document

    DNP V3.0 Device Profile 2.2 Device Profile Document Device Profile Document DNP V3.0 DEVICE PROFILE DOCUMENT SIEMENS AG Vendor Name: Device Name: 7SD80 Highest DNP Level Supported: Device Function: For Requests DNP-L2 Master Slave For Responses DNP-L2 Notable objects, functions, and/or qualifiers supported in addition to the Highest DNP Levels Supported (the...
  • Page 19 DNP V3.0 Device Profile 2.2 Device Profile Document Requires Application Layer Confirmation: Never Always (not recommended) When reporting Event Data (Slave devices only) When sending multi-fragment responses (Slave devices only) Sometimes If 'Sometimes', when? ___________________________________ Configurable If 'Configurable', how? by the protection data processing program DIGSI 4 Timeouts while waiting for: Data Link Confirm None...
  • Page 20 DNP V3.0 Device Profile 2.2 Device Profile Document Reports Binary Input Change Events when no Reports time-tagged Binary Input Change Events specific variation requested: when no specific variation requested: Never Never Only time-tagged Binary Input Change With Time Only non-time-tagged Binary Input Change With Relative Time Configurable to send both, one or the...
  • Page 21: Point Lists

    Point lists Binary Input Points Control Relay Output Blocks/Binary Output Status Analog Inputs SIPROTEC, 7SD80, Bus mapping DNP 3.0 C53000-L2040-C347-1, Edition 07.2011...
  • Page 22: 3.1 Binary Input Points

    3 Point lists 3.1 Binary Input Points Binary Input Points Binary Input Points Static (Steady-State) Object Number: 1 Change Event Object Number: 2 Request Function Codes supported: 1 (read) Static Variation reported when variation 0 requested: 1 (Binary Input with status) Change Event Variation reported when variation 0 requested: 2 (Binary Input Change with Time) Point Name...
  • Page 23: Thermal Overload Protection

    3 Point lists 3.1 Binary Input Points Binary Input Points Static (Steady-State) Object Number: 1 Change Event Object Number: 2 Request Function Codes supported: 1 (read) Static Variation reported when variation 0 requested: 1 (Binary Input with status) Change Event Variation reported when variation 0 requested: 2 (Binary Input Change with Time) Point Name Description...
  • Page 24: Internal Mode Status

    3 Point lists 3.1 Binary Input Points Binary Input Points Static (Steady-State) Object Number: 1 Change Event Object Number: 2 Request Function Codes supported: 1 (read) Static Variation reported when variation 0 requested: 1 (Binary Input with status) Change Event Variation reported when variation 0 requested: 2 (Binary Input Change with Time) Point Name Description...
  • Page 25 3 Point lists 3.1 Binary Input Points Binary Input Points Static (Steady-State) Object Number: 1 Change Event Object Number: 2 Request Function Codes supported: 1 (read) Static Variation reported when variation 0 requested: 1 (Binary Input with status) Change Event Variation reported when variation 0 requested: 2 (Binary Input Change with Time) Point Name Description...
  • Page 26: Control Relay Output Blocks/Binary Output Status

    3 Point lists 3.2 Control Relay Output Blocks/Binary Output Status Control Relay Output Blocks/Binary Output Status Binary Output Status Points Object Number: 10 Request Function Codes supported: 1 (Read) Default Variation reported when variation 0 requested: 2 (Binary Output Status) Control Relay Output Blocks/Binary Output Status Object Number: 12 Request Function Codes supported: 3 (select), 4 (operate), 5 (direct operate),...
  • Page 27: Analog Inputs

    3 Point lists 3.3 Analog Inputs Analog Inputs Analog Inputs Static (Steady-State) Object Number: 30 Change Event Object Number: 32 Request Function Codes supported: 1 (read) Static Variation reported when variation 0 requested: 02 (16-Bit Analog Input) Change Event Variation reported when variation 0 requested:02 (Analog Change Event without Time) Point Name Description...
  • Page 28 3 Point lists 3.3 Analog Inputs SIPROTEC, 7SD80, Bus mapping DNP 3.0 C53000-L2040-C347-1, Edition 07.2011...
  • Page 29 Glossary Asynchronous interface module with (electrical) isolated RS485 interface for the SIPROTEC devices from Siemens. Asynchronous interface module with optical interface for the SIPROTEC devices from Siemens. Automatic Recloser Continuous Function Chart Double Command DIGSI Parameterization system for SIPROTEC devices...
  • Page 30 Single Command Single-point Indication SIPROTEC, 7SD80, Bus mapping DNP 3.0 C53000-L2040-C347-1, Edition 07.2011...
  • Page 31 Index Zahlen Scaling values 12 Setting group 11 79 22 Stop data transmission 10 Subset Level 2 16 Subset Level 3 16 Alarm summary event 10 Summary alarm 10 Analog Inputs 12, 27 Symbol conventions 6 Applicability of manual 4 Target audience of manual 3 Binary Input Points 10, 22 Typographic conventions 6...
  • Page 32 SIPROTEC, 7SD80, Bus mapping DNP 3.0 C53000-L2040-C347-1, Edition 07.2011...