Siemens siprotec 7SD5 User Manual page 456

Line differential protection with distance protection
Hide thumbs Also See for siprotec 7SD5:
Table of Contents

Advertisement

3 Mounting and Commissioning
Table 3-3
Depending on the device version the contacts of some binary outputs can be changed
from normally open to normally closed (see Appendix, under Section A.2).
• In versions 7SD5***-*D/H/M (housing size
• In versions 7SD5***-*C/G/L (housing size
• In versions 7SD5***-*P/R/T (housing size
Table 3-4 shows the jumper settings for the contact mode.
Table 3-4
Jumper settings for contact mode of the binary outputs BO16 and BO24 on the input/output board C–I/O-1
Device
Printed Circuit
7SD5***–*
Board
D/H/M
Slot 19 left side BO 16
Slot 19 right
side
C/G/L
Slot 19 right
side
P/R/T
Slot 19 left side BO 24
456
Jumper
60/110/125 VDC
Fuse
Jumper settings of the Life Contact on the input/output board C-I/O-1
Open in Quiescent State
Jumper
(NO)
X40
the binary outputs BO16 and BO24 (Figure 3-4, slot 19 left and right);
the binary output BO16 (Figure 3-4, slot 19 right);
acceleration) this is valid for the binary output BO24 (Figure 3-4, slot 19 left).
For
Jumper
Open in Quies-
cent State (NO)
X40
BO 24
X40
BO 16
X40
X40
Nominal Voltage
110/125/220/250 VDC 115 VAC
Interchangeable
T2H250V
Closed in Quiescent State
1-2
1
/
with 32 binary outputs) this is valid for
1
1
/
with 24 binary outputs) this is valid for
1
1
/
with 32 binary outputs and command
1
Closed in Quiescent State
(NC)
1-2
2-3
1-2
2-3
1-2
2-3
1-2
2-3
24/48 VDC
Cannot be
changed
T4H250V
Factory Setting
(NC)
2-3
2-3
Factory
Setting
1-2
1-2
1-2
1-2
7SD5 Manual