3101
IC comp. active
3102
2nd Harmonic L1
3103
2nd Harmonic L2
3104
2nd Harmonic L3
3120
Diff active
3132
Diff. Gen. Flt.
3133
Diff. Flt. L1
3134
Diff. Flt. L2
3135
Diff. Flt. L3
3136
Diff. Flt. E
3137
I-Diff>> Flt.
3139
I-Diff> Flt.
3141
Diff. Gen. TRIP
3142
Diff TRIP 1p L1
3143
Diff TRIP 1p L2
3144
Diff TRIP 1p L3
3145
Diff TRIP L123
3146
Diff TRIP 1pole
3147
Diff TRIP 3pole
3148
Diff block
3149
Diff OFF
3176
Diff Flt. 1p.L1
3177
Diff Flt. L1E
3178
Diff Flt. 1p.L2
3179
Diff Flt. L2E
3180
Diff Flt. L12
3181
Diff Flt. L12E
3182
Diff Flt. 1p.L3
3183
Diff Flt. L3E
3184
Diff Flt. L31
3185
Diff Flt. L31E
3186
Diff Flt. L23
3187
Diff Flt. L23E
3188
Diff Flt. L123
3189
Diff Flt. L123E
3190
Test Diff.
3191
Comm. Diff
3192
TestDiff.remote
3193
Comm.Diff act.
3194
>Test Diff.
3195
>Comm. Diff
3525
> Diff block
3526
Diffblk.rec PI1
3527
Diffblk.rec PI2
104
Type of In-
formation
OUT
IC compensation active
OUT
Diff: 2nd Harmonic detected in phase L1
OUT
Diff: 2nd Harmonic detected in phase L2
OUT
Diff: 2nd Harmonic detected in phase L3
OUT
Diff: Active
OUT
Diff: Fault detection
OUT
Diff: Fault detection in phase L1
OUT
Diff: Fault detection in phase L2
OUT
Diff: Fault detection in phase L3
OUT
Diff: Earth fault detection
OUT
Diff: Fault detection of I-Diff>>
OUT
Diff: Fault detection of I-Diff>
OUT
Diff: General TRIP
OUT
Diff: TRIP - Only L1
OUT
Diff: TRIP - Only L2
OUT
Diff: TRIP - Only L3
OUT
Diff: TRIP L123
OUT
Diff: TRIP 1pole
OUT
Diff: TRIP 3pole
OUT
Diff: Differential protection is blocked
OUT
Diff: Diff. protection is switched off
OUT
Diff: Fault detection L1 (only)
OUT
Diff: Fault detection L1E
OUT
Diff: Fault detection L2 (only)
OUT
Diff: Fault detection L2E
OUT
Diff: Fault detection L12
OUT
Diff: Fault detection L12E
OUT
Diff: Fault detection L3 (only)
OUT
Diff: Fault detection L3E
OUT
Diff: Fault detection L31
OUT
Diff: Fault detection L31E
OUT
Diff: Fault detection L23
OUT
Diff: Fault detection L23E
OUT
Diff: Fault detection L123
OUT
Diff: Fault detection L123E
IntSP
Diff: Set Teststate of Diff. protection
IntSP
Diff: Set Commissioning state of Diff.
OUT
Diff: Remote relay in Teststate
OUT
Diff: Commissioning state is active
SP
Diff: >Test Diff.
SP
Diff: >Comm. Diff
SP
>Differential protection blocking signal
OUT
Differential blocking received at PI1
OUT
Differential blocking received at PI2