3 Mounting and Commissioning
3.1.3.3

Panel Surface Mounting

For mounting proceed as follows:
• Secure the device to the panel with four screws. For dimensions see the Technical
• Connect the earth of the device to the protective earth of the panel. The cross-sec-
• Connect solid, low-impedance operational earthing (cross-sectional area ≥ 2.5
• Make the connections according to the circuit diagram via the screwed-type termi-
470
Data in Section 4.25.
tional area of the earth wire must be equal to the cross-sectional area of any other
conductor connected to the device. The cross-section of the earth wire must be at
2
least 2.5 mm
.
2
mm
) to the earthing surface on the side. Use at least one M4 screw for the device
earth.
nals. Fibre-optic cables and electrical communication modules are connected at the
inclined housings. The SIPROTEC
regarding wire size, lugs, bending radii, etc. You will find hints in the short descrip-
tion included in the device.
®
4 System Description has pertinent information
7SD5 Manual
C53000-G1176-C169-1