2.23.3.4 Setting Notes

Fault
Pickup of a new protective function generally turns off any previously lit LEDs, so that
Annunciations
only the latest fault is displayed at any time. It can be selected whether the stored LED
displays and the spontaneous annunciations on the display appear upon renewed
pickup, or only after a renewed trip signal is issued. In order to enter the desired type
of display, select the submenu General Device Settings in the SETTINGS menu. At
address 610 FltDisp.LED/LCD the two alternatives Target on PU and Target
on TRIP („No trip - no flag") are offered.
For devices with graphical display use parameter 615 Spont. FltDisp. to specify
whether or not a spontaneous annunciation will appear automatically on the display
(YES) or not (NO). For devices with text display such messages will appear after a
system fault in any case.
After startup of a device featuring a 4-line display, measured values are displayed by
default. Use the arrow keys on the device front to select the different represenations
of the measured values for the so-called default display. The start page of the default
display, which is displayed by default after startup of the device, can be selected via
parameter 640 Start image DD. The available representation types for the mea-
sured values are listed in the appendix .

2.23.3.5 Settings

Addr.
Parameter
610
FltDisp.LED/LCD
615
Spont. FltDisp.
640
Start image DD

2.23.3.6 Information List

No.
Information
-
Test mode
-
DataStop
-
UnlockDT
-
SynchClock
-
>Light on
-
HWTestMod
-
Error FMS1
-
Error FMS2
-
Brk OPENED
-
FdrEARTHED
3
>Time Synch
412
Setting Options
Target on PU
Target on TRIP
NO
YES
image 1
image 2
image 3
image 4
image 5
image 6
Type of In-
formation
IntSP
Test mode
IntSP
Stop data transmission
IntSP
Unlock data transmission via BI
IntSP_Ev
Clock Synchronization
SP
>Back Light on
IntSP
Hardware Test Mode
OUT
Error FMS FO 1
OUT
Error FMS FO 2
IntSP
Breaker OPENED
IntSP
Feeder EARTHED
SP
>Synchronize Internal Real Time Clock
Default Setting
Target on PU
Fault Display on LED / LCD
NO
Spontaneous display of flt.annun-
ciations
image 1
Start image Default Display
Comments
Comments
7SD5 Manual
C53000-G1176-C169-1