Siemens siprotec 7SD5 User Manual page 620

Line differential protection with distance protection
Hide thumbs Also See for siprotec 7SD5:
Table of Contents

Advertisement

A Appendix
Addr.
Parameter
402A
WAVEFORMTRIGGER
403A
WAVEFORM DATA
410
MAX. LENGTH
411
PRE. TRIG. TIME
412
POST REC. TIME
415
BinIn CAPT.TIME
610
FltDisp.LED/LCD
615
Spont. FltDisp.
640
Start image DD
1103
FullScaleVolt.
1104
FullScaleCurr.
1105
Line Angle
1106
OPERATION POWER
1107
P,Q sign
1111
x'
1111
x'
1112
c'
1112
c'
1113
Line Length
1113
Line Length
1114
Tot.Line Length
1114
Tot.Line Length
1116
RE/RL(Z1)
1117
XE/XL(Z1)
1118
RE/RL(Z1B...Z5)
1119
XE/XL(Z1B...Z5)
1120
K0 (Z1)
1121
Angle K0(Z1)
1122
K0 (> Z1)
1123
AngleI K0(> Z1)
1124
center phase
1125
C0/C1
620
Function
C
Setting Options
Osc. Fault Rec.
Save w. Pickup
Save w. TRIP
Start w. TRIP
Osc. Fault Rec.
Fault event
Pow.Sys.Flt.
Osc. Fault Rec.
0.30 .. 5.00 sec
Osc. Fault Rec.
0.05 .. 0.50 sec
Osc. Fault Rec.
0.05 .. 0.50 sec
0.10 .. 5.00 sec; ∞
Osc. Fault Rec.
Device
Target on PU
Target on TRIP
Device
NO
YES
Device
image 1
image 2
image 3
image 4
image 5
image 6
P.System Data 2
0.4 .. 1200.0 kV
P.System Data 2
10 .. 5000 A
30 .. 89 °
P.System Data 2
P.System Data 2
0.2 .. 5000.0 MVA
P.System Data 2
not reversed
reversed
0.0050 .. 9.5000 Ω/km
P.System Data 2
1A
0.0010 .. 1.9000 Ω/km
5A
0.0050 .. 15.0000 Ω/mi
P.System Data 2
1A
0.0010 .. 3.0000 Ω/mi
5A
0.000 .. 100.000 µF/km
P.System Data 2
1A
0.000 .. 500.000 µF/km
5A
0.000 .. 160.000 µF/mi
P.System Data 2
1A
0.000 .. 800.000 µF/mi
5A
P.System Data 2
0.1 .. 1000.0 km
P.System Data 2
0.1 .. 650.0 Miles
P.System Data 2
0.1 .. 1000.0 km
P.System Data 2
0.1 .. 650.0 Miles
P.System Data 2
-0.33 .. 7.00
P.System Data 2
-0.33 .. 7.00
P.System Data 2
-0.33 .. 7.00
P.System Data 2
-0.33 .. 7.00
P.System Data 2
0.000 .. 4.000
-135.00 .. 135.00 °
P.System Data 2
P.System Data 2
0.000 .. 4.000
-135.00 .. 135.00 °
P.System Data 2
P.System Data 2
unknown/sym.
Phase 1
Phase 2
Phase 3
P.System Data 2
0.01 .. 10.00
Default Setting
Save w. Pickup
Waveform Capture
Fault event
Scope of Waveform Data
2.00 sec
Max. length of a Waveform
Capture Record
0.25 sec
Captured Waveform Prior to
Trigger
0.10 sec
Captured Waveform after Event
0.50 sec
Capture Time via Binary Input
Target on PU
Fault Display on LED / LCD
NO
Spontaneous display of flt.an-
nunciations
image 1
Start image Default Display
400.0 kV
Measurement: Full Scale Voltage
(100%)
1000 A
Measurement: Full Scale Current
(100%)
85 °
Line Angle
692.8 MVA
Operational power of protection
zone
not reversed
P,Q operational measured values
sign
0.1500 Ω/km
x' - Line Reactance per length
unit
0.0300 Ω/km
0.2420 Ω/mi
x' - Line Reactance per length
unit
0.0484 Ω/mi
0.010 µF/km
c' - capacit. per unit line len.
µF/km
0.050 µF/km
0.016 µF/mi
c' - capacit. per unit line len.
µF/mile
0.080 µF/mi
100.0 km
Line Length
62.1 Miles
Line Length
100.0 km
Total Line Length
62.1 Miles
Total Line Length
1.00
Zero seq. comp. factor RE/RL for
Z1
1.00
Zero seq. comp. factor XE/XL for
Z1
1.00
Zero seq. comp.factor RE/RL for
Z1B...Z5
1.00
Zero seq. comp.factor XE/XL for
Z1B...Z5
1.000
Zero seq. comp. factor K0 for
zone Z1
0.00 °
Zero seq. comp. angle for zone
Z1
1.000
Zero seq.comp.factor K0,higher
zones >Z1
0.00 °
Zero seq. comp. angle, higher
zones >Z1
unknown/sym.
center phase of feeder
0.75
Compensation factor C0/C1
C53000-G1176-C169-1
Comments
7SD5 Manual