Siemens siprotec 7SD5 User Manual page 636

Line differential protection with distance protection
Hide thumbs Also See for siprotec 7SD5:
Table of Contents

Advertisement

A Appendix
Addr.
Parameter
4515A
PI1 BLOCK UNSYM
4601
STATE PROT I 2
4602
CONNEC. 2 OVER
4605A
PROT 2 T-DELAY
4606A
PROT 2 UNSYM.
4611
PI2 SYNCMODE
4613A
PROT2 max ERROR
4615A
PI2 BLOCK UNSYM
4701
ID OF RELAY 1
4702
ID OF RELAY 2
4703
ID OF RELAY 3
4704
ID OF RELAY 4
4705
ID OF RELAY 5
4706
ID OF RELAY 6
4710
LOCAL RELAY
4801
GPS-SYNC.
4803A
TD GPS FAILD
6001
S1: Line angle
6002
S1: x'
6002
S1: x'
6003
S1: c'
6003
S1: c'
6004
S1: Line length
6004
S1: line length
6008
S1: center ph.
6009
S1: XE/XL
6010
S1: RE/RL
6011
S1: K0
6012
S1: angle K0
6021
S2: Line angle
6022
S2: x'
6022
S2: x'
636
Function
C
Setting Options
Prot. Interface
YES
NO
Prot. Interface
ON
OFF
Prot. Interface
F.optic direct
Com conv 64 kB
Com conv 128 kB
Com conv 512 kB
Prot. Interface
0.1 .. 30.0 ms
Prot. Interface
0.000 .. 3.000 ms
Prot. Interface
TEL and GPS
TEL or GPS
GPS SYNC OFF
Prot. Interface
0.5 .. 20.0 %
Prot. Interface
YES
NO
Diff.-Topo
1 .. 65534
Diff.-Topo
1 .. 65534
Diff.-Topo
1 .. 65534
Diff.-Topo
1 .. 65534
Diff.-Topo
1 .. 65534
Diff.-Topo
1 .. 65534
Diff.-Topo
relay 1
relay 2
relay 3
relay 4
relay 5
relay 6
Prot. Interface
ON
OFF
Prot. Interface
0.5 .. 60.0 sec
30 .. 89 °
P.System Data 2
0.0050 .. 9.5000 Ω/km
P.System Data 2
1A
0.0010 .. 1.9000 Ω/km
5A
0.0050 .. 15.0000 Ω/mi
P.System Data 2
1A
0.0010 .. 3.0000 Ω/mi
5A
0.000 .. 100.000 µF/km
P.System Data 2
1A
0.000 .. 500.000 µF/km
5A
0.000 .. 160.000 µF/mi
P.System Data 2
1A
0.000 .. 800.000 µF/mi
5A
P.System Data 2
0.1 .. 1000.0 km
P.System Data 2
0.1 .. 650.0 Miles
P.System Data 2
unknown/sym.
Phase 1
Phase 2
Phase 3
P.System Data 2
-0.33 .. 7.00
P.System Data 2
-0.33 .. 7.00
P.System Data 2
0.000 .. 4.000
-135.00 .. 135.00 °
P.System Data 2
30 .. 89 °
P.System Data 2
0.0050 .. 9.5000 Ω/km
P.System Data 2
1A
0.0010 .. 1.9000 Ω/km
5A
0.0050 .. 15.0000 Ω/mi
P.System Data 2
1A
0.0010 .. 3.0000 Ω/mi
5A
Default Setting
YES
Prot.1: Block. due to unsym.
delay time
ON
State of protection interface 2
F.optic direct
Connection 2 over
30.0 ms
Prot 2: Maximal permissible
delay time
0.100 ms
Prot 2: Diff. in send and receive
time
TEL and GPS
PI2 Synchronizationmode
1.0 %
Prot 1: Maximal permissible error
rate
YES
Prot.2: Block. due to unsym.
delay time
1
Identification number of relay 1
2
Identification number of relay 2
3
Identification number of relay 3
4
Identification number of relay 4
5
Identification number of relay 5
6
Identification number of relay 6
relay 1
Local relay is
OFF
GPS synchronization
2.1 sec
Delay time for local GPS-pulse
loss
85 °
S1: Line angle
0.1500 Ω/km
S1: feeder reactance per km: x'
0.0300 Ω/km
0.2420 Ω/mi
S1: feeder reactance per mile: x'
0.0484 Ω/mi
0.010 µF/km
S1: feeder capacitance c' in
µF/km
0.050 µF/km
0.016 µF/mi
S1: feeder capacitance c' in
µF/mile
0.080 µF/mi
100.0 km
S1: Line length in kilometer
62.1 Miles
S1: Line length in kilometer
unknown/sym.
S1: center phase
1.00
S1: Zero seq. compensating
factor XE/XL
1.00
S1: Zero seq. compensating
factor RE/RL
1.000
S1: Zero seq. compensating
factor K0
0.00 °
S1: Zero seq. compensating
angle of K0
85 °
S2: Line angle
0.1500 Ω/km
S2: feeder reactance per km: x'
0.0300 Ω/km
0.2420 Ω/mi
S2: feeder reactance per mile: x'
0.0484 Ω/mi
C53000-G1176-C169-1