Setting Notes; Settings; Information List - Siemens siprotec 7SD5 User Manual

Line differential protection with distance protection
Hide thumbs Also See for siprotec 7SD5:
Table of Contents

Advertisement

2 Functions
2.4.2

Setting Notes

General
The intertrip function for tripping caused by the differential protection can be activated
(YES) or deactivated (NO) with address 1301 I-TRIP SEND. Since the differential pro-
tection devices theoretically operate with the same measured values at all ends of the
protected object, a tripping in the event of an internal fault normally is also carried out
at all ends, regardless of the infeed conditions at the ends. In special cases, i.e. if fault
currents are to be expected near to the pickup threshold, it may occur that one or more
ends do not issue a tripping command due to inevitable device tolerances. For these
cases I-TRIP SEND = YES ensures the tripping at all ends of the protected object.
Intertrip/Remote
If the intertrip function is activated, it will automatically start when the differential pro-
Tripping
tection trips.
If the relevant binary inputs are allocated and activated by an external source, the in-
tertrip signal is transmitted as well. In this case, the signal to be transmitted can be
delayed with address 1303 T-ITRIP BI. This delay stabilizes the originating signal
against dynamic interferences which may possibly occur on the control cabling.
Address 1304 T-ITRIP PROL BI is used to extend a signal after it has been effec-
tively injected from an external source.
The reaction of a device when receiving an intertrip/remote tripping signal is set in
address 1302 I-TRIP RECEIVE. If it is supposed to cause tripping, set the value
Trip. If the received signal, however, is supposed to cause an alarm only, Alarm
only must be set even if this annunciation is to be further processed externally.
The setting times depend on the individual case of application. A delay is necessary if
the external control signal originates from a disturbed source and a restraint seems
appropriate. Of course, the control signal has to be longer than the delay for the signal
to be effective. If the signal is processed externally at the receiving end, a prolongation
time might become necessary for the transmitting end so that the reaction desired at
the receiving end can be executed reliably.
2.4.3

Settings

Addr.
Parameter
1301
I-TRIP SEND
1302
I-TRIP RECEIVE
1303
T-ITRIP BI
1304
T-ITRIP PROL BI
2.4.4

Information List

No.
Information
3501
>Intertrip L1
3502
>Intertrip L2
108
Setting Options
YES
NO
Alarm only
Trip
0.00 .. 30.00 sec
0.00 .. 30.00 sec
Type of In-
formation
SP
I.Trip: >Intertrip L1 signal input
SP
I.Trip: >Intertrip L2 signal input
Default Setting
NO
State of transmit. the intertrip
command
Trip
Reaction if intertrip command is
receiv.
0.02 sec
Delay for intertrip via binary input
0.00 sec
Prolongation for intertrip via
bin.input
Comments
Comments
7SD5 Manual
C53000-G1176-C169-1

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents