Siemens siprotec 7SD5 User Manual page 628

Line differential protection with distance protection
Hide thumbs Also See for siprotec 7SD5:
Table of Contents

Advertisement

A Appendix
Addr.
Parameter
2916A
T V-Supervision
2921
T mcb
2931
BROKEN WIRE
FAST Σ i SUPERV
2933
3101
FCT EarthFltO/C
3102
BLOCK for Dist.
3103
BLOCK 1pDeadTim
3104A
Iph-STAB. Slope
3105
3IoMin Teleprot
3105
3IoMin Teleprot
3109
Trip 1pole E/F
3110
Op. mode 3I0>>>
3111
3I0>>>
3112
T 3I0>>>
3113
3I0>>> Telep/BI
3114
3I0>>>SOTF-Trip
3115
3I0>>>InrushBlk
3120
Op. mode 3I0>>
3121
3I0>>
3122
T 3I0>>
3123
3I0>> Telep/BI
3124
3I0>> SOTF-Trip
3125
3I0>> InrushBlk
3130
Op. mode 3I0>
3131
3I0>
3131
3I0>
3132
T 3I0>
3133
3I0> Telep/BI
3134
3I0> SOTF-Trip
3135
3I0> InrushBlk
628
Function
C
Setting Options
Measurem.Superv
0.00 .. 30.00 sec
Measurem.Superv
0 .. 30 ms
Measurem.Superv
ON
OFF
Measurem.Superv
ON
OFF
Earth Fault O/C
ON
OFF
Earth Fault O/C
every PICKUP
1phase PICKUP
multiph. PICKUP
NO
Earth Fault O/C
YES
NO
Earth Fault O/C
0 .. 30 %
Earth Fault O/C
1A
0.01 .. 1.00 A
5A
0.05 .. 5.00 A
Earth Fault O/C
1A
0.003 .. 1.000 A
5A
0.015 .. 5.000 A
Earth Fault O/C
YES
NO
Earth Fault O/C
Forward
Reverse
Non-Directional
Inactive
Earth Fault O/C
1A
0.05 .. 25.00 A
5A
0.25 .. 125.00 A
0.00 .. 30.00 sec; ∞
Earth Fault O/C
Earth Fault O/C
NO
YES
Earth Fault O/C
NO
YES
Earth Fault O/C
NO
YES
Earth Fault O/C
Forward
Reverse
Non-Directional
Inactive
Earth Fault O/C
1A
0.05 .. 25.00 A
5A
0.25 .. 125.00 A
0.00 .. 30.00 sec; ∞
Earth Fault O/C
Earth Fault O/C
NO
YES
Earth Fault O/C
NO
YES
Earth Fault O/C
NO
YES
Earth Fault O/C
Forward
Reverse
Non-Directional
Inactive
Earth Fault O/C
1A
0.05 .. 25.00 A
5A
0.25 .. 125.00 A
Earth Fault O/C
1A
0.003 .. 25.000 A
5A
0.015 .. 125.000 A
0.00 .. 30.00 sec; ∞
Earth Fault O/C
Earth Fault O/C
NO
YES
Earth Fault O/C
NO
YES
Earth Fault O/C
NO
YES
Default Setting
3.00 sec
Delay Voltage Failure Supervi-
sion
0 ms
VT mcb operating time
OFF
Fast broken current-wire supervi-
sion
ON
State of fast current summation
supervis
ON
Earth Fault overcurrent function
is
every PICKUP
Block E/F for Distance protection
YES
Block E/F for 1pole Dead time
10 %
Stabilisation Slope with Iphase
0.50 A
3Io-Min threshold for Teleprot.
schemes
2.50 A
0.500 A
3Io-Min threshold for Teleprot.
schemes
2.500 A
YES
Single pole trip with earth flt.prot.
Inactive
Operating mode
4.00 A
3I0>>> Pickup
20.00 A
0.30 sec
T 3I0>>> Time delay
NO
Instantaneous trip via Tele-
prot./BI
NO
Instantaneous trip after Switch-
OnToFault
NO
Inrush Blocking
Inactive
Operating mode
2.00 A
3I0>> Pickup
10.00 A
0.60 sec
T 3I0>> Time Delay
NO
Instantaneous trip via Tele-
prot./BI
NO
Instantaneous trip after Switch-
OnToFault
NO
Inrush Blocking
Inactive
Operating mode
1.00 A
3I0> Pickup
5.00 A
1.000 A
3I0> Pickup
5.000 A
0.90 sec
T 3I0> Time Delay
NO
Instantaneous trip via Tele-
prot./BI
NO
Instantaneous trip after Switch-
OnToFault
NO
Inrush Blocking
C53000-G1176-C169-1
Comments
7SD5 Manual