2.22.2.2 Setting Notes

General
The number of circuits to be supervised was set during the configuration in address
140 Trip Cir. Sup. (Section 2.1.1.3). If the trip circuit supervision is not used at
all, the setting Disabled must be applied there.
The trip circuit supervision can be switched ON or OFF in address 4001 FCT
TripSuperv.. The number of binary inputs that shall be used in each of the super-
vised circuits is set in address 4002 No. of BI. If the routing of the binary inputs
required for this does not comply with the selected supervision mode, an alarm is
given („TripC1 ProgFAIL ...", with identification of the non-compliant circuit).
Supervision with
The alarm for supervision with two binary inputs is always delayed by approx. 1 s to
One Binary Input
2 s, whereas the delay time of the alarm for supervision with one binary input can be
set in address 4003 Alarm Delay. 1 s to 2 s are sufficient if only the 7SD5 device is
connected to the trip circuits as the trip circuit supervision does not operate during a
system fault. If, however, trip contacts from other devices are connected in parallel in
the trip circuit, the alarm must be delayed such that the longest trip command duration
can be reliably bridged.

2.22.2.3 Settings

Addr.
Parameter
4001
FCT TripSuperv.
4002
No. of BI
4003
Alarm Delay

2.22.2.4 Information List

No.
Information
6854
>TripC1 TripRel
6855
>TripC1 Bkr.Rel
6856
>TripC2 TripRel
6857
>TripC2 Bkr.Rel
6858
>TripC3 TripRel
6859
>TripC3 Bkr.Rel
6861
TripC OFF
6865
FAIL: Trip cir.
6866
TripC1 ProgFAIL
6867
TripC2 ProgFAIL
6868
TripC3 ProgFAIL
7SD5 Manual
C53000-G1176-C169-1
Setting Options
ON
OFF
1 .. 2
1 .. 30 sec
Type of In-
formation
SP
>Trip circuit superv. 1: Trip Relay
SP
>Trip circuit superv. 1: Breaker Relay
SP
>Trip circuit superv. 2: Trip Relay
SP
>Trip circuit superv. 2: Breaker Relay
SP
>Trip circuit superv. 3: Trip Relay
SP
>Trip circuit superv. 3: Breaker Relay
OUT
Trip circuit supervision OFF
OUT
Failure Trip Circuit
OUT
TripC1 blocked: Binary input is not set
OUT
TripC2 blocked: Binary input is not set
OUT
TripC3 blocked: Binary input is not set
2.22 Monitoring Functions
Default Setting
OFF
TRIP Circuit Supervision is
2
Number of Binary Inputs per trip
circuit
2 sec
Delay Time for alarm
Comments
Comments
395