Siemens siprotec 7SD5 User Manual page 563

Line differential protection with distance protection
Hide thumbs Also See for siprotec 7SD5:
Table of Contents

Advertisement

Undervoltage Positive Sequence System U
Undervoltage U
<<
1
Delay T
U1<<
Undervoltage U
<
1
Delay T
U1<
Dropout ratio
Current criterion
Pickup times (fast relays/high-speed relays)
Dropout time
Tolerances
7SD5 Manual
C53000-G1176-C169-1
4.17 Undervoltage and Overvoltage Protection (optional)
1
1.0 V to 100.0 V
0.00 s to 100.00 s; ∞
1.0 V to 100.0 V
0.00 s to 100.00 s; ∞
approx. 1.05
Can be switched on/off
approx. 35/30 ms
approx. 30 ms
Voltages
3 % of setting value or 1 V
Times
1 % of setting value or 10 ms
Increments 0.1 V
Increments 0.01 s
Increments 0.1 V
Increments 0.01 s
563