Information List; Trip Circuit Supervision - Siemens siprotec 7SD5 User Manual

Line differential protection with distance protection
Hide thumbs Also See for siprotec 7SD5:
Table of Contents

Advertisement

Addr.
Parameter
2915
V-Supervision
2916A
T V-Supervision
2921
T mcb
2931
BROKEN WIRE
FAST Σ i SUPERV
2933

2.22.1.7 Information List

No.
Information
161
Fail I Superv.
163
Fail I balance
164
Fail U Superv.
Fail Σ U Ph-E
165
167
Fail U balance
168
Fail U absent
169
VT FuseFail>10s
170
VT FuseFail
171
Fail Ph. Seq.
196
Fuse Fail M.OFF
197
MeasSup OFF
Failure Σi
289
290
Broken Iwire L1
291
Broken Iwire L2
292
Broken Iwire L3
295
Broken wire OFF
Σi superv. OFF
296

2.22.2 Trip Circuit Supervision

The line protection 7SD5 is equipped with an integrated trip circuit supervision func-
tion. Depending on the number of available binary inputs (not connected to a common
potential), supervision with one or two binary inputs can be selected. If the routing of
the binary inputs required for this does not comply with the selected supervision mode,
an alarm is given („TripC1 ProgFAIL ...", with identification of the non-compliant cir-
cuit). When using two binary inputs, malfunctions in the trip circuit can be detected
under all circuit breaker conditions. When only one binary input is used, malfunctions
in the circuit breaker itself cannot be detected. If single-pole tripping is possible, a sep-
arate trip circuit supervision can be implemented for each circuit breaker pole provided
the required binary inputs are available.
7SD5 Manual
C53000-G1176-C169-1
C
Setting Options
w/ CURR.SUP
w/ I> & CBaux
OFF
0.00 .. 30.00 sec
0 .. 30 ms
ON
OFF
ON
OFF
Type of In-
formation
OUT
Failure: General Current Supervision
OUT
Failure: Current Balance
OUT
Failure: General Voltage Supervision
OUT
Failure: Voltage summation Phase-Earth
OUT
Failure: Voltage Balance
OUT
Failure: Voltage absent
OUT
VT Fuse Failure (alarm >10s)
OUT
VT Fuse Failure (alarm instantaneous)
OUT
Failure: Phase Sequence
OUT
Fuse Fail Monitor is switched OFF
OUT
Measurement Supervision is switched OFF
OUT
Alarm: Current summation supervision
OUT
Alarm: Broken current-wire detected L1
OUT
Alarm: Broken current-wire detected L2
OUT
Alarm: Broken current-wire detected L3
OUT
Broken wire supervision is switched OFF
OUT
Current summation superv is switched OFF
2.22 Monitoring Functions
Default Setting
w/ CURR.SUP
Voltage Failure Supervi-
sion
3.00 sec
Delay Voltage Failure Su-
pervision
0 ms
VT mcb operating time
OFF
Fast broken current-wire
supervision
ON
State of fast current sum-
mation supervis
Comments
Comments
391