Automatic Reclosure Function (Optional) - Siemens siprotec 7SD5 User Manual

Line differential protection with distance protection
Hide thumbs Also See for siprotec 7SD5:
Table of Contents

Advertisement

4 Technical Data
4.15

Automatic Reclosure Function (optional)

Automatic Reclosures
Number of reclosures
Type (depending on ordered version)
Control
Action times
Initiation possible without pickup and action time
Different dead times before
reclosure can be set for all operating modes and
cycles
Dead times after evolving fault recognition
Reclaim time after reclosure
Blocking time after dynamic blocking
Blocking time after manual closing
Start signal monitoring time
Circuit breaker monitoring time
Adaptive Dead Time / Dead Line Check
Adaptive dead time
Action times
Initiation possible without pickup and action time
Maximum dead time
Voltage measurement dead line or bus
Voltage measurement live or bus
Voltage measuring time
Time delay for close command transmission
558
Max. 8,
first 4 with individual settings
1-pole, 3-pole or 1-/3-pole
With pickup or trip command
0.01 s to 300.00 s; ∞
0.01 s to 1800.00 s; ∞
0.01 s to 1800.00 s
0.50 s to 300.00 s
0.5 sec
0.50 s to 300.00 s; 0
0.01 s to 300.00 s
0.01 s to 300.00 s
With voltage measurement or
with close command transmission
0.01 s to 300.00 s; ∞
0.50 s to 3000.00 s
2 V to 70 V (Ph-E)
30 V to 90 V (Ph-E)
0.10 s to 30.00 s
0.00 to 300.00; ∞
Increments 0.01 s
Increments 0.01 s
Increments 0.01 s
Increments 0.01 s
Increments 0.01 s
Increments 0.01 s
Increments 0.01 s
Increments 0.01 s
Increments 0.01 s
Increments 1 V
Increments 1 V
Increments 0.01 s
Increments 0.01 s
7SD5 Manual
C53000-G1176-C169-1

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents