Siemens siprotec 7SD5 User Manual page 496

Line differential protection with distance protection
Hide thumbs Also See for siprotec 7SD5:
Table of Contents

Advertisement

3 Mounting and Commissioning
Figure 3-27
Local and remote measured values in the WEB-Monitor — examples for plausible measured values
Polarity Check
If the device is connected with voltage transformers, the local measured values
already provide a polarity test.
For more than two ends, one current path is continued to be tested first. A load current
of at least 5% of the rated operational current is required. Any direction is possible but
must be known.
496
7SD5 Manual
C53000-G1176-C169-1