Settings; Information List - Siemens siprotec 7SD5 User Manual

Line differential protection with distance protection
Hide thumbs Also See for siprotec 7SD5:
Table of Contents

Advertisement

2 Functions
2.9.8

Settings

Addresses which have an appended "A" can only be changed with DIGSI, under Ad-
ditional Settings.
Addr.
Parameter
3201
FCT Telep. E/F
3202
Line Config.
3203A
Send Prolong.
3207A
Delay for alarm
3208
Release Delay
3209A
TrBlk Wait Time
3210A
TrBlk BlockTime
2.9.9

Information List

No.
Information
1311
>EF Teleprot.ON
1312
>EF TeleprotOFF
1313
>EF TeleprotBLK
1318
>EF Rec.Ch1
1319
>EF Rec.Ch2
1320
>EF UB ub 1
1321
>EF UB bl 1
1322
>EF UB ub 2
1323
>EF UB bl 2
1324
>EF BlkEcho
1325
>EF Rec.Ch1 L1
1326
>EF Rec.Ch1 L2
1327
>EF Rec.Ch1 L3
1328
>EF UB ub 1-L1
1329
>EF UB ub 1-L2
1330
>EF UB ub 1-L3
1371
EF Tele SEND L1
1372
EF Tele SEND L2
1373
EF Tele SEND L3
1374
EF Tele STOP L1
1375
EF Tele STOP L2
1376
EF Tele STOP L3
1380
EF TeleON/offBI
1381
EF Telep. OFF
248
Setting Options
ON
OFF
Two Terminals
Three terminals
0.00 .. 30.00 sec
0.00 .. 30.00 sec
0.000 .. 30.000 sec
0.00 .. 30.00 sec; ∞
0.00 .. 30.00 sec
Type of In-
formation
SP
>E/F Teleprotection ON
SP
>E/F Teleprotection OFF
SP
>E/F Teleprotection BLOCK
SP
>E/F Carrier RECEPTION, Channel 1
SP
>E/F Carrier RECEPTION, Channel 2
SP
>E/F Unblocking: UNBLOCK, Channel 1
SP
>E/F Unblocking: BLOCK, Channel 1
SP
>E/F Unblocking: UNBLOCK, Channel 2
SP
>E/F Unblocking: BLOCK, Channel 2
SP
>E/F BLOCK Echo Signal
SP
>E/F Carrier RECEPTION, Channel 1, Ph.L1
SP
>E/F Carrier RECEPTION, Channel 1, Ph.L2
SP
>E/F Carrier RECEPTION, Channel 1, Ph.L3
SP
>E/F Unblocking: UNBLOCK Chan. 1, Ph.L1
SP
>E/F Unblocking: UNBLOCK Chan. 1, Ph.L2
SP
>E/F Unblocking: UNBLOCK Chan. 1, Ph.L3
OUT
E/F Telep. Carrier SEND signal, Phase L1
OUT
E/F Telep. Carrier SEND signal, Phase L2
OUT
E/F Telep. Carrier SEND signal, Phase L3
OUT
E/F Telep. Block: carrier STOP signal L1
OUT
E/F Telep. Block: carrier STOP signal L2
OUT
E/F Telep. Block: carrier STOP signal L3
IntSP
E/F Teleprot. ON/OFF via BI
OUT
E/F Teleprotection is switched OFF
Default Setting
ON
Teleprotection for Earth Fault O/C
Two Terminals
Line Configuration
0.05 sec
Time for send signal prolongation
10.00 sec
Unblocking: Time Delay for Alarm
0.000 sec
Time Delay for release after
pickup
0.04 sec
Transient Block.: Duration exter-
nal flt.
0.05 sec
Transient Block.: Blk.T. after ext.
flt.
Comments
Comments
7SD5 Manual