Quinta Pro 45 - 65 - 90 - 115
5.7
Changing the settings
Parameter
Description
Flow temperature: T
p1
Open vented:
p1
Flow temperature: T
Domestic hot water temperature:
p2
T
SET
Heating / DHW mode
p3
Mode ECO
p4
Anticipation resistance
p5
Display screen
p6
Post-circulation of the pump
p7
Brightness of display lighting
p8
Maximum ventilator speed
p17
(Heating)
(1) Do not modify these factory settings unless absolutely necessary. For example, for modification of the boiler for: G20 (H gas) or G31 (propane),
high pressure systems, WTW coupling or CLV overpressure
080310 - 123157-AA
The boiler control panel is set for the most common heating
systems. With these settings, practically all heating systems operate
correctly. The user or installer can optimise the parameters according
to own preferences.
For operation in open vented systems, several parameter settings
must be adjusted. Set the various parameters according to the values
given in the table below.
5.7.1.
Adjustment range
20 to 90 °C
SET
20 to 90 °C
SET
40 to 65 °C
0 = Heating deactivated / DHW deactivated
1 = Heating activated / DHW activated
2 = Heating activated / DHW deactivated
3 = Heating deactivated / DHW activated
0 = Comfort
1 = Energy-saving mode
2 = Management using a programmable thermostat
0 = No anticipation resistance for the ON/OFF
thermostat
1 = Anticipation resistance for the ON/OFF
thermostat
0 = Simple
1 = Comprehensive
2 = Automatic switching to simple after 3 minutes
3 = Automatic switching to simple after 3 minutes ;
Key blocking is active
1 to 98 minutes
99 minutes = continuous
0 = Dimmed
1 = Bright
G25 (Gas L)
(x100 rpm)
G20 (Gas H)
(x100 rpm)
G31 (Propane)
(x100 rpm)
Description of the parameters
(1)
5. Start-up
Factory setting
Quinta Pro
30 45 65 90 115
80
75
60
1
2
0
2
1
1
xx 52 52 62
70
xx 52 52 62
70
xx 52 52 62
70
63